12-79
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.9 Error code list (7000 to 10000)
7004
[MULTI CPU DOWN]
In a multiple CPU system, a data error occurred in
communication between the CPU modules.
■Collateral information
•Common Information:Module No.(CPU No.)
•Individual Information:–
■Diagnostic Timing
•Always
•Check the system configuration to see if modules
are mounted in excess of the number of I/O
points.
•When there are no problems in the system
configuration, this indicates the CPU module
hardware is faulty. (Contact your local Mitsubishi
representative, explaining a detailed description
of the problem.)
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Q00/Q01*1
QnU*6
7010
[MULTI EXE. ERROR]
•In a multiple CPU system, a faulty CPU module
was mounted.
•In a multiple CPU system, a CPU module
incompatible with the multiple CPU system was
mounted. (The CPU module compatible with the
multiple CPU system was used to detect an
error.)
•In a multiple CPU system, any of the CPU No. 2
to 4 was reset with power ON. (The CPU whose
reset state was cancelled was used to detect an
error.)
■Collateral information
•Common Information:Module No.(CPU No.)
•Individual Information:–
■Diagnostic Timing
•At p ower ON/At reset
•Read the individual information of the error using
GX Developer, and replace the faulty CPU
module.
•Replace the CPU module with the one
compatible with the multiple CPU system.
•Do not reset any of the No. 2 to 4 CPU modules.
•Reset CPU No. 1 and restart the multiple CPU
system.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Q00/Q01*1
Qn(H)*1
QnPH
QnU*6
[MULTI EXE. ERROR]
The PC CPU module-compatible software package
(PPC-DRV-01)*5 whose version is 1.06 or earlier is
used in a multiple CPU system.
■Collateral information
•Common Information:Module No.(CPU No.)
•Individual Information:–
■Diagnostic Timing
•At p ower ON/At reset
Change the version of the PC CPU module-
compatible software package (PPC-DRV-01)*5 to
1.07 or later.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Q00/Q01*1
[MULTI EXE. ERROR]
The Q172(H)CPU(N) or Q173(H)CPU(N) is
mounted on the multiple CPU high-speed main
base unit (Q3 DB). (This may result in a module
failure.)
■Collateral information
•Common Information:Module No.(CPU No.)
•Individual Information:–
■Diagnostic Timing
•At p ower ON/At reset
Replace the Q172(H)CPU(N) and Q173(H)CPU(N)
with the Motion CPU compatible with the multiple
CPU high-speed main base unit.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)*4
QnPH*4
[MULTI EXE. ERROR]
The Universal model QCPU (except Q02UCPU)
and Q172(H)CPU(N) are mounted on the same
base unit. (This may result in a module failure.)
■Collateral information
•Common Information:Module No.(CPU No.)
•Individual Information:–
■Diagnostic Timing
•At p ower ON/At reset
Check the QCPU and Motion CPU that can be
used in a multiple CPU system, and change the
system configuration.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Error
Code
(SD0)
Error Contents and Cause Corrective Action LED Status
CPU Status
Corresponding
CPU
*1 The function version is B or later.
*4 The module whose first 5 digits of serial No. is "09082" or later.
*6 The Universal model QCPU except the Q00UJCPU.