Specifications
Generator Specifications |
| |||||
| ||||||
Design |
|
| Revolving field, | |||
|
|
| ||||
|
|
|
| |||
No. of Poles |
|
|
|
| ||
Excitation |
|
|
| Brushless with AVR |
| |
Standby Output |
|
|
| 110 KW (137 KVA) |
| |
Prime Output |
|
|
| 100 KW (125 KVA) |
| |
Generator RPM |
| 1800 |
|
| ||
Voltage — 3Ø |
| 208, 220, 240, 416, 440, 480V Switchable | ||||
Voltage — 1Ø |
| 120, 127, 139, 240, 254, 277V Switchable | ||||
Armature Connection |
|
|
| Star with neutral / Zig Zag | ||
Voltage Regulation |
| ±0.5% |
|
| ||
(No load to full load) |
|
|
| |||
|
|
|
|
|
| |
Power Factor |
| 0.8 |
|
| ||
Frequency |
|
|
| 60 Hz |
| |
Frequency Regulation: |
| Isochronous under varying loads from | ||||
No Load to Full Load |
|
|
| no load to 100% rated load | ||
Frequency Regulation: |
| ±0.25% of mean value for constant loads | ||||
Steady State |
|
|
| from no load to full load | ||
Insulation |
|
|
| Class F |
| |
Sound Level dB(A) |
| 65 |
|
| ||
Full load at 23 feet |
|
|
| |||
|
|
|
|
|
| |
|
|
|
|
|
| |
Engine Specifications |
|
|
|
|
| |
Make/Model |
|
| Isuzu / 4HK1X |
| ||
Emissions |
|
| EPA Tier 3 Certified | |||
Starting System |
|
| Electric |
| ||
Design |
| |||||
| turbocharged, air to air intercooled | |||||
|
|
| ||||
Displacement |
|
| 5193 cc |
| ||
No. cylinders |
| 4 |
|
| ||
Bore x Stroke (mm) |
|
| 115 x 125 |
| ||
Gross Engine Power Output |
|
| 170.3 hp (127 kW) | |||
HP at Rated Speed |
|
| 152.3 hp (113.6 kW) | |||
BMEP |
|
| 212 psi (1458 kPa) | |||
Piston Speed |
|
| 1480 ft/min (7.50 m/s) | |||
Compression Ratio |
| 17.5 : 1 |
| |||
Engine Speed |
|
| 1800 rpm |
| ||
Overspeed Limit |
|
| 2070 rpm |
| ||
Oil capacity gallons (liters) |
| 6.1 (23.4) |
| |||
Battery |
|
| 12V 128 Ah x 1 |
| ||
|
|
|
|
|
|
|
Fuel System |
|
|
|
|
| |
Recommended Fuel |
|
| ||||
Maximum Fuel Flow (per hour) |
|
| 19.0 gal (71.0 L) | |||
Maximum Inlet Restriction (Hg) |
|
| 8.9 in (225 mm) | |||
Fuel Tank Capacity |
|
| 169 gal (640 L) | |||
Fuel Consumption |
|
| gph |
| lph | |
at full load |
|
| 7.3 |
| 27.6 | |
at 3/4 load |
|
| 5.7 |
| 21.7 | |
at 1/2 load |
|
| 4.0 |
| 15.1 | |
at 1/4 load |
|
| 2.4 |
| 9.1 | |
DCA125USI Rev 2 |
|
|
|
|
|
Cooling System
Fan Load | 4.4 hp (3.3 kW) | |
Coolant Capacity (with radiator) | 5.2 | gal (19.7 L) |
Coolant Flow Rate (per minute) | 48 | gal (180 L) |
|
| |
Heat Rejection to Coolant (per minute) | 3500 Btu (3.7 MJ) | |
Heat Rejection from Engine (per minute) | 1040 Btu (1.1 MJ) | |
Maximum Coolant Friction Head | 6.5 psi (45.0 kPa) | |
Maximum Coolant Static Head | 29.5 ft (9.0 m) | |
Ambient Temperature Rating | 104°F (40°C) | |
|
|
|
Air
Combustion Air | 297 cfm (8.4 m3/min) |
Maximum Air Cleaner Restriction | 25.0 in H2O (6.25 kPa) |
Alternator Cooling Air | 1352 cfm (38.3 m3/min) |
Radiator Cooling Air | 2944 cfm (83 m3/min) |
Exhaust System
Gas Flow (full load) | 738 cfm (20.9 m3/min) |
Gas Temperature | 986°F (530°C) |
Maximum Back Pressure | 53.2 in/H2O (13.3 kPa) |
Amperage
Rated Voltage | Maximum Amps |
1Ø 120 Volt | 277.8 Amps (4 wire) |
|
|
1Ø 240 Volt | 138.9 Amps (4 wire) |
3Ø 240 Volt | 300 Amps |
3Ø 480 Volt | 150 Amps |
|
|
Main Line Circuit Breaker Rating | 300 Amps |
Over Current Relay Trip Set Point | 152 Amps |
|
|
Warranty*
Isuzu Engine
12 months from date of purchase with unlimited hours or 24 months from date of purchase with 2000 hours (whichever comes first).
Generator
24 months from date of purchase or 2000 hours (whichever occurs first).
Trailer
12 months excluding normal wear items.
*Refer to the express written,
Generator is not intended for use in enclosed areas or where free flow of air is restricted.
Backfeed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system except through an approved device.