INSTALLATION

OUTDOOR INSTALLATION

Install the generator in a area that is free of debris, bystanders, and overhead obstructions. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear to engine and alternator parts.

CAUTION

Pay close attention to ventilation when operating the generator inside tunnels and caves.The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

INDOOR INSTALLATION

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside. The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

MOUNTING

The generator must be mounted on a solid foundation (such as concrete) and set fi rmly on the foundation to isolate vibration of the generator when it is running.The generator must set at least 6 inches above the fl oor or grade level (in accordance to NFPA 110, Chapter 5-4.1). DO NOT remove the metal skids on the bottom of the generator. They are to resist damage to the bottom of the generator and to maintain alignment.

GENERATOR GROUNDING

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifi es that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 250-64(b) and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper - 8 AWG (5.3 mm2)

b.Aluminum - 6 AWG (8.4 mm2)

2.When grounding the generator (Figure 2) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried a minimum of 8 ft. into the ground.

NOTICE

When connecting the generator to any buildings electrical system ALWAYS consult with a licensed electrician.

DCA45USI2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (01/12/11) — PAGE 15

Page 15
Image 15
Multiquip DCA45USI2 manual Outdoor Installation, Indoor Installation, Mounting, Generator Grounding

DCA45USI2 specifications

The Multiquip DCA45USI2 is a robust and versatile generator that caters to a wide array of power needs across various applications. Designed for both commercial and industrial use, this generator stands out due to its powerful output, durability, and advanced technology.

The DCA45USI2 offers a maximum output of 45 kVA, making it suitable for both demanding construction sites and as a backup power source for critical equipment in emergencies. It operates with a reliable Yanmar diesel engine, known for its fuel efficiency and longevity, ensuring that users can count on consistent performance over extended periods. The unit is built to provide high-quality electrical output, ensuring that sensitive equipment is protected from surges and fluctuations.

One of the standout features of the DCA45USI2 is its sound attenuation technology. Enclosed within a sturdy yet compact frame, this generator is designed to minimize noise levels, making it an ideal choice for urban environments or noise-sensitive applications. The insulation materials used are specifically chosen to absorb sound waves while still allowing for efficient ventilation.

In terms of ease of use, the DCA45USI2 is equipped with a user-friendly control panel that provides comprehensive monitoring capabilities. This includes advanced protective features, such as low oil pressure shutdown, high-temperature shutdown, and overload protection, ensuring that the generator operates safely at all times. The digital display offers real-time information on vital operating parameters, enabling operators to swiftly respond to any issues that may arise.

Another key characteristic of the DCA45USI2 is its portability. Weighing in at a manageable level for its size and capacity, it features heavy-duty wheels and a lifting eye which allow for easy transportation across job sites. This adaptability is crucial for rental companies and contractors who require a reliable source of power on-the-go.

Overall, the Multiquip DCA45USI2 embodies a blend of power, efficiency, and convenience. Its advanced engineering and thoughtful design cater to the needs of various industries, making it a preferred choice among professionals who demand reliability and performance from their equipment. Whether for construction, emergency response, or temporary power solutions, the DCA45USI2 proves to be a formidable ally in getting the job done efficiently and effectively.