AUTOSTART 710 (AS710S) series
PROGRAMMABLE GENERATOR CONTROLLER
The Autostart 710 provides the control features needed for the automatic start, load transfer and shutdown of a standby generator or pump. Microprocessor technology allows the Autostart 710 to be programmed for use in a wide range of engine and generator control applications.
Key features
∙Automatic or manual operation, selected by
∙32 character,
∙Full programmability of engine control options, timers,
trip levels, fault options and input/output configurations
∙Comprehensive fault protection and alarm system:- low oil pressure and high engine temperature alarms (using analogue or switch sensors), engine overspeed and underspeed, emergency stop, start fail, charge fail, high and low battery voltage, 3 programmable fault inputs.
∙6 programmable outputs, each configurable to one
of over 30 function types.
∙Pin compatibility with Keystart 9700 range, allowing standardisation of panel wiring
Operation
The AS710’s operating mode is selected by use of a 3 position switch:–
Off/reset. Removes power from the unit, disabling the engine and resetting a latched fault condition.
Automatic
Manual start and stop of the generator, either immediately on selecting manual mode or by use of remote push button switches.
Green and amber LEDs around the switch indicate the selection of Auto or Manual modes. On keyswitch versions, the key is common to all units and is removable in the Off and Auto positions only.
Control Outputs
The following outputs are provided:-
∙Single pole, switched +ve relay outputs for the control of engine fuel and starter motor circuits.
∙Switched +ve outputs for signalling auto and manual modes, plus a
∙6 function programmable outputs (see overleaf).
Fault Protection and Alarm System
In Auto or Manual modes, Autostart shuts down and latches out the generator on detection of low oil pressure, high engine temperature, overspeed, start fail or emergency stop faults. The Autostart may also be set up to shut down the generator on a low generator frequency or speed condition.
3 additional inputs may be used with remote fault switches (giving a ‘shutdown’ or ‘warning’ response), or as control inputs with remote contacts or panel switches (see overleaf).
Product Specification
Power supply:
Operating voltage: steady state range | 5 – 40 V DC continuous, | |
crank |
| to 0 V for <= 100 mSec |
Current consumption |
| typically 150 mA |
Inputs: |
|
|
DC inputs (inputs 1 - 5, mains fail): |
|
|
positive input voltage range |
| 80% to 100% of battery +ve |
negative input voltage range |
| |
Generator AC input: |
|
|
operating voltage range |
| 90 – 300 V AC rms |
frequency measurement range |
| 0 – 99 Hz. |
Magnetic pickup: |
|
|
operating voltage range |
| 7 – 80 V AC rms |
frequency measurement range |
| 0 – 10 kHz |
Outputs: |
| (all ratings for resistive load) |
Start and fuel relays | + ve DC (switched SPNO contact) | |
|
| 16A max. @ 24 V DC |
Programmable outputs 1 – 3 | – ve DC (open collector transistor) | |
|
| 250mA max. @ 33 V DC |
Programmable output 4 | – ve DC (switched SPNO contact) | |
|
| 5A max. @ 24 V DC |
Programmable output 5 | + ve DC (switched SPNO contact) | |
(default setting: common alarm) |
| 5A max. @ 24 V DC |
Programmable output 6 |
| volt free SPNO relay contacts |
(default setting: gen. contactor) |
| 5A max. @ 240 V AC |
Auto & Manual outputs | + ve DC (switched), 250 mA max. | |
Off/reset output | – ve DC (switched), 250 mA max. | |
General: |
|
|
Overall dimensions (W x H x D) |
| 96 x 96 x 162 mm |
Panel |
| DIN standard 92 x 92 mm |
Weight |
| approx. 650 g |
Operating ambient temperature |
| |
Case sealing |
| IP22 |
|
|
|