Temperature Scanner/Pyrometer SWICHGAGE | Revised | |
® Catalog Section 10 | ||
| ||
|
| |
|
|
Model TDX6
Approved *
Approved**
Description
The TDX6 is an advanced design
selector allows the operator to set
and view each trip point. With the selector in the scan mode, a “thermocouple read” push button
provides a means to manually toggle through the six channels and to lock in on a specific chan- nel. Normal scanning will resume
approximately three seconds after releasing the push button. All trip points are continually armed and active during the scanning process.
Type “J” or “K”, grounded† or ungrounded thermocouples are accommodated. Other types are available upon request.
The TDX6 can interface with other Murphy SELECTRONIC® TATTLETALE® annunciators and
Applications
• Gas Compressor | • Process Temperatures |
Suction/Discharge Temp. | • Generators |
• Engine/Compressor Jacket | • Pumps |
Water Temperature | • Engine Exhaust Temperature |
Features
■Monitors six (6) input sensors
■Accepts type “J” or “K” thermocouples grounded† or ungrounded
■Field adjustable trip points
■LCD display in either °F or °C (specify)
■One thermocouple maybe selected for continuous display
■CD ignition, 24 VDC, or 120 VAC powered
■No special training or programming required
•Scans 6 Channels
•Adjustable Trip Points
•“J” or “K” Thermocouples
•Powered by CD Ignition, 24 VDC, or 120 VAC
•Rated for Class I, Division 2, Group D Hazardous Areas
•
•Easy to Read Digital Display
*When used with approved ignition. Contact Murphy for details.
**When used with power requirements described below.
■Scans all 6 sensors in 30 seconds
Specifications
Power Requirements (Operating Voltages): 120 VAC or
Outputs:
Models
Models
Operating Temperature:
Storage Temperature:
Case: ABS 1/4 DIN (90 x 90 mm).
Scanning Speed: Complete scan in 30 seconds.
Reset Differential: F.E.T. models: Decreases 3 Degrees (°F or °C). S.C.R. models: Turn input power off to reset.
Display Update Time: Updates temperature every 0.3 seconds.
Ambient Cold Junction Compensation Range:
2°F from 32°F to 122°F (1°C from 0°C to 50°C).
Measurement Range: Monitor Range
Accuracy:
With
With
Trip Point Accuracy: ±3°F (±2°C) of reading.
Trip Point Adjustment Range: 0-1999 Degrees.
Open Thermocouple Input: A number 1 appears in the display
†to the right of the channel number and the trip point operates. Using grounded thermocouples introduces the risk of odd currents or voltages
being imposed on the thermocouple signal which can affect the accuracy of the reading. This is an inherent problem of grounded thermocouples, the reason why we prefer ungrounded thermocouples.