Easy to Read Digital Display
Thermocouple
Read
Trip Point
Read/Scan
Trip Point
Adjustment

 

TDX-9106B

Temperature Scanner/Pyrometer SWICHGAGE

Revised 11-02

® Catalog Section 10

(00-02-0049)

 

 

 

 

 

Model TDX6

Approved *

Approved**

Description

The TDX6 is an advanced design 6-point temperature scanner and pyrometer. It continually scans up to six thermocouples and sequentially displays the thermocouple number and its reading. Each sensor input has a field settable trip point for alarm, shut- down or control. A read/scan

selector allows the operator to set

and view each trip point. With the selector in the scan mode, a “thermocouple read” push button

provides a means to manually toggle through the six channels and to lock in on a specific chan- nel. Normal scanning will resume

approximately three seconds after releasing the push button. All trip points are continually armed and active during the scanning process.

Type “J” or “K”, groundedor ungrounded thermocouples are accommodated. Other types are available upon request.

The TDX6 can interface with other Murphy SELECTRONIC® TATTLETALE® annunciators and Micro-controllers. It is rated for Class I, Division 2, Group D, hazardous areas* and is available for operation from CD ignition, 120 VAC, or 24 VDC.

Applications

Gas Compressor

Process Temperatures

Suction/Discharge Temp.

Generators

Engine/Compressor Jacket

Pumps

Water Temperature

Engine Exhaust Temperature

Features

Monitors six (6) input sensors

Accepts type “J” or “K” thermocouples groundedor ungrounded

Field adjustable trip points

LCD display in either °F or °C (specify)

One thermocouple maybe selected for continuous display

CD ignition, 24 VDC, or 120 VAC powered

No special training or programming required

Scans 6 Channels

Adjustable Trip Points

“J” or “K” Thermocouples

Powered by CD Ignition, 24 VDC, or 120 VAC

Rated for Class I, Division 2, Group D Hazardous Areas

Start-up Time Delay

Easy to Read Digital Display

*When used with approved ignition. Contact Murphy for details.

**When used with power requirements described below.

Scans all 6 sensors in 30 seconds

Specifications

Power Requirements (Operating Voltages): 120 VAC or 80-250 VDC, CD ignition or 24 VDC.

Outputs:

Models TDX6-A and TDX6-C: Six (6) isolated Silicon Controlled Rectifier (S.C.R.) outputs; 0.5 A @ 250 VDC; switches on (applies ground) above trip point and switches off (removes ground) when power is switched off.

Models TDX6-B and TDX6-D:Six (6) isolated Field-Effect Transistor (F.E.T.) outputs; 0.1 A @ 250 VDC; switches on (applies ground) above trip point and switches off (removes ground) below trip point.

Operating Temperature: -4 to 158°F (-20 to 70°C).

Storage Temperature: -40 to 300°F (-40 to 150°C).

Case: ABS 1/4 DIN (90 x 90 mm).

Scanning Speed: Complete scan in 30 seconds.

Reset Differential: F.E.T. models: Decreases 3 Degrees (°F or °C). S.C.R. models: Turn input power off to reset.

Display Update Time: Updates temperature every 0.3 seconds.

Start-up Time Delay: Unit is locked out for 10 seconds after ignition voltage is sensed.

Ambient Cold Junction Compensation Range:

2°F from 32°F to 122°F (1°C from 0°C to 50°C).

Measurement Range: Monitor Range 0-1999°F or °C (specify °F or °C in part number).

Accuracy:

With J-type thermocouple: from 50-150°F (10-66°C) +3°F(+2°C), from 150-1200°F (66-649°C) ±1.0% of reading.

With K-type thermocouple: from 400-2000°F(204-1076°C) ±1.0% of reading.

Trip Point Accuracy: ±3°F (±2°C) of reading.

Trip Point Adjustment Range: 0-1999 Degrees.

Open Thermocouple Input: A number 1 appears in the display

to the right of the channel number and the trip point operates. Using grounded thermocouples introduces the risk of odd currents or voltages

being imposed on the thermocouple signal which can affect the accuracy of the reading. This is an inherent problem of grounded thermocouples, the reason why we prefer ungrounded thermocouples.

Page 1