FieldPoint Operating Instructions

FP-AI-112 and cFP-AI-112
16-Channel, 16-Bit Analog Input Modules
These operating instructions describe how to install and use the
FP-AI-112 and cFP-AI-112 analog input modules (referred
toinclusively as the [c]FP-AI-112). For information about
configuring and accessing the [c]FP-AI-112 over a network, refer
to the user manual for the FieldPoint network module you are
using.

Features

The [c]FP-AI-112 is a FieldPoint analog input module with the
following features:
16 analog voltage input channels
Eight voltage input ranges: 0–1V, 0–5 V, 0–10V, ±60 mV,
±300mV, ±1V, ±5V, and ±10V
16-bit resolution
50 and 60 Hz filter settings
250Vrms CAT II continuous channel-to-ground isolation,
verified by 2,300Vrms,1 minute dielectric withstand test
–40 to 70 °C operation
Hot swappable

Installing the FP-AI-112

The FP-AI-112 mounts on a FieldPoint terminal base (FP-TB-x),
which provides operating power to the module. Installing the
FP-AI-112 onto a powered terminal base does not disrupt the
operation of the FieldPoint bank.