© National Instruments Corp. 3 FP-AI-112 and cFP-AI-112
3. Using a number 2 Phillips screwdriver with a shank of at least
64mm (2.5 in.) length, tighten the captive screws to 1.1 N m
(10 lbin.) of torque. The nylon coating on the screws prevents
them from loosening.
Figure 2. Installing the cFP-AI-112
Wiring the [c]FP-AI-112
The FP-TB-x terminal base has connections for each of the
16input channels and for an optional external power supply to
power field devices. The cFP-CB-x connector block provides the
same connections. Each channel has one input terminal (VIN) for
voltage input. All 16 inputs are referenced to the COM terminals,
which are internally connected to each other and to the C terminals.
The channels share eightVSUP terminals, all of which are internally
connected to each other and to the V terminals.
1cFP-AI-112
2 Captive Screws
3 cFP Controller Module
4 Screw Holes
5 cFP Backplane
2
2
1
3 5
4
4