FP-QUAD-510 10 www.ni.com
As with any hazardous voltage wiring, make sure that all
wiring and connections meet applicable electrical codes and
common sense practices. Mount terminal bases in an area,
position, or cabinet that prevents accidental or unauthorized
access to wiring that carries hazardous voltages.
The isolation of the FP-QUAD-510 is certified as
double-insulated for normal operating voltages of 250 Vrms.
Do not use the FP-QUAD-510 as the only isolating barrier
between human contact and working voltages of more than
250Vrms.
Channel Operation Summary
Table3 summarizes the functionality of each of the FP-QUAD-510
channels as accessed through FieldPoint Explorer or other
software.
Table 3. FP-QUAD-510 Channel Operation Summary
Channel
No. Channel Description Type Range
0Axis 0 Position LSW Count Input 0–65535
1Axis 1 Position LSW Count Input 0–65535
2Axis 2 Position LSW Count Input 0–65535
3Axis 3 Position LSW Count Input 0–65535
4Axis 0 Position MSW Count Input 0–65535
5Axis 1 Position MSW Count Input 0–65535
6Axis 2 Position MSW Count Input 0–65535
7Axis 3 Position MSW Count Input 0–65535
8Axis 0 Velocity Analog Input 8 ranges
9Axis 1 Velocity Analog Input 8 ranges
10 Axis 2 Velocity Analog Input 8 ranges
11 Axis 3 Velocity Analog Input 8 ranges
12 Axis 0 Index Active Discrete Input Boolean
13 Axis 1 Index Active Discrete Input Boolean
14 Axis 2 Index Active Discrete Input Boolean
15 Axis 3 Index Active Discrete Input Boolean