FieldPoint is a trademark of National Instruments Corporation. Product and company names
mentioned herein are trademarks or trade names of their respective companies.
321904B-01 © Copyright 1998, 1999 National Instruments Corp. All rights reserved. June 1999

OPERATING INSTRUCTIONS

FP-RLY-420

8-Channel, SPST Relay Module

These operating instructions describe the installation, features, and
characteristics of the FP-RLY-420. For details on configuring and
accessing the FP-RLY-420 ov er a network, refer to the user manual
forthe particular FieldPoint network module you are using with
the FP-RLY-420.

Features

The FP-RLY-420 is a FieldPoint relay output module with the
following features:
Eight Single-Pole Single-Throw (SPST) relay channels
Switching capacity 3 A at 35 VDC or 250 VAC
On/Off LED indicators
Hot plug and play operation
3,000 V input to output isolation
Double insulated for 250 V safe working voltage
–40 to +70 °C operation

Power Requirement

The FP-RLY-420 is powered via the local backplane bus from the
FieldPoint network module. The FP-RLY-420 is a high-power
consumption module and requires more than the nominal power
allocated to an I/O module from the network module. In some
applications, this could limit the number of I/O modules that you
can connect to a single network module.
When defining a FieldPoint system that uses an FP-RLY-420
module, you must calculate the power consumption. First refer
tothe specifications section in the user manual for your network