NI 9481 Operating Instructions and Specifications 14 ni.com
Physical CharacteristicsIf you need to clean the module, wipe it with a dry towel.
Screw-terminal wiring...................... 12 to 24 AWG copper
conductor wire with 10 mm
(0.39 in.) of insulation
stripped from the end
Torque for screw terminals ............... 0.5 to 0.6 N · m
(4.4to 5.3 lb · in.)
Ferrules............................... ..............0.25 mm2 to 2.5 mm2
Weight...............................................150 g (5.3 oz)
SafetySafety Voltages
Connect only voltages that are within the following limits.
CHa-to-CHb......................................250 Vrms max,
MeasurementCategory II
Measurement Category II is for measurements performed on
circuits directly connected to the electrical distribution system.
This category refers to local-level electrical distribution, such as