Using the Isolated Loop Supply of the SCC-CO20
You can connect the SCC-CO20 to a load using either the isolated internal loop supply or an external supply. The internal loop supply outputs a voltage of 15 V with respect to the isolated ground reference. When using the internal loop supply, the compliance voltage is 12.5 V. This allows for a maximum load resistance of 625 Ω at 20 mA. Figure 2 shows how to connect the SCC-CO20, using the internal loop supply, to a nonreferenced (floating) load and to a load with a high common-mode voltage.
| SCC-CO20 | | |
| | |
| 3 | SUPPLY |
| + | | | | | |
| | | | 0–20 mA | Load |
| 15 V iso |
| – | | |
| 2 | | |
| SINK |
| | | | |
| | | | |
| | | | |
| | | | | | |
1
I
SCC-CO20 | |
| |
3 | SUPPLY |
+ | | | | |
15 V iso | 0–20 mA |
– | |
2 | |
| | | | SINK |
| | | |
| | | |
| | | | |
1
I
Figure 2. Connecting the SCC-CO20 Using the Internal Loop Supply