Figure 1. SCC-RLY01 Circuit Diagram

Caution When connecting signals >60 VDC to the SCC-RLY01 module in the SCC-68, you must use the high-voltage backshell. Figure 2 shows the high-voltage backshell.

Figure 2. High-Voltage Backshell

For information about how to configure the SCC-RLY01 module with

NI-DAQmx, refer to the SCC Quick Start Guide.

Specifications

These ratings are typical at 25 °C unless otherwise stated.

Electrical

Contact type............................................

SPDT (Form C), nonlatching

Nominal switching capacity

 

SCC-68 ............................................

5 A at 250 VAC

 

5 A at 30 VDC

SC-2345...........................................

5 A at 30 VAC

 

5 A at 30 VDC

SCC-RLY01 Relay Module User Guide