ND-71548 (E) CHAPTER 2
Page 31
Issue 2
INSTALLATION DESIGN
Note: Selection of T-Type Clamp Terminal
The asterisk (*) in Table 2-9 indicates that an auxiliary conductor is necessary when using a main power
wire and a branch power wire of a thinner diameter, and the clamp terminal of the type indicated in the
selected columns.
Table 2-9 Selection of T-type Clamp Terminal
BRANCH
MAIN
14 AWG/
2 mm2
12 AWG/
3.5 mm2
10 AWG/
5.5 mm2
8 AWG/
8 mm2
6 AWG/
14 mm2CURRENT REMARKS
10 AWG *T-20 *T-20 *T-20 - - 51A
8 AWG *T-20 *T-20 *T-20 T-20 - 63 A
6 AWG T-20 T-20 T-20 T-26 T-44 90 A
3 AWG T-26 T-26 T-44 T-44 T-44 115A
2 A WG *T-44 T-44 T- 44 T- 44 T-4 4 1 39 A
1 AWG *T-44 *T-44 T-44 T-66 T-60 162A
1ø *T-60 T-60 T-60 T-60 T-76 190A
2ø *T-76 T-76 T-76 T-76 T-76 217A
3ø *T-98 *T-98 *T-98 T-98 T-98 257A
4ø *T-122 *T-122 *T-122 *T-122 T-122 298A
250 mcm *T-154 *T-154 *T-154 T-154 T-154 344A
300 mcm *T-154 *T-190 *T-190 *T-190 T-190 395A
400 mcm *T-240 *T-240 *T-240 *T-240 T-240 439A