ND-71548 (E) CHAPTER 3
Page 79
Issue 2
INSTALLATION PROCEDURE
3. END JOINTING OF POWER AND GROUND CABLES
NAP-200-008
Sheet 8/13
Connection of Power and Ground
Cables from the Power Equipment
START
Stripping of Insulation Sheath Strip the wire to exceed the length of the terminal body
by 1 - 2 mm (1/8 inch).
Clamping Referring to Figure 008-6, place the terminal body on
the die with the soldered part facing upward.
Referring to Figure 008-7, insert the stripped wire into
the terminal body up to the insulation-sheath edge, and
clamp the terminal.
Wipe the terminal with a dry cloth.
END
WIRE SHEATH
CONDUCTOR
CLAMP TERMINAL
1/8 inch (1 - 2 mm)