Figure #16

(Life varies from 500 to 2000 operating hours, as illustrated in Figure #16.)

The RESDELUX control board constantly monitors unit performance and will shut down the humidifier and alert the customer to change the cylinder. The yellow light will flash 4 times in sequence.

Figure #16

Water Conditions vs. Cylinder Life

Capacity Adjustment Setting

 

 

100%

50%

25%

 

 

30

 

 

 

500

 

 

 

 

 

 

 

 

 

 

400

ofHardness

20

 

 

 

 

 

 

 

 

200 mg/L(ppm)

Grains

10

 

 

 

3

 

 

 

CaCO

 

 

 

 

 

5

 

 

 

100

 

 

 

 

 

 

500

1000

2000

4000

8000

 

 

Cylinder Life Expectancy

 

(average operating hours)

HOW TO REMOVE THE STEAM CYLINDER

It is advisable to keep a spare cylinder in stock throughout the humidification season. When ordering a replacement steam cylinder, always quote the three or five digit model number on the label applied to the

Figure #17

Cylinder Replacement

cylinder or quote the unit’s serial number, model and voltage located on the spec label (nameplate).

1.Turn off the water supply to the unit.

2.The used cylinder must be drained completely before removal. If the water has just been boiling, allow it to cool before draining. Push the ON/OFF/DRAIN switch to the MANUAL DRAIN position. Leave it in this position just long enough to drain the cylinder (usually not longer than 3 minutes).

3.When completely drained, push the main ON/OFF/DRAIN switch back to the OFF position.

4.Once drained, disconnect all power supplies to the unit.

5.Open the front cover door.

6.Cylinder plugs are attached to the primary voltage cylinder wires. Remove cylinder plugs from cylinder pins by pulling vertically.

7.Using a slotted screwdriver, loosen the steam hose clamp(s) and pull the steam hose off the cylinder vertically.

8.The cylinder is now ready to be lifted out of the unit. CAUTION: Cylinder and any undrained water might still be HOT.

9.Remove the used cylinder as previously described. NORTEC does not recommend the use of any acid solutions to clean the used cylinder. Always replace a used cylinder.

HOW TO INSTALL THE REPLACEMENT CYLINDER

1.Reverse procedure should be followed to install a new cylinder. Main power supply to the unit must be disconnected until the cylinder is completely installed and reconnected.

2.The cylinder plug wires are color-coded in accordance with colored dots beside the electrode pins on the top of the cylinder.

Figure #18

Reassembly Of The Drain Valve And Fill Valve

 

Actuator

 

 

 

Male Slip-on

 

 

Connection Tabs

Plunger

Spring

Sleeve

 

 

 

 

Holding Coil

- 9 -

Page 12
Image 12
Nortec Steam Humidifiers manual Figure #16 Water Conditions vs. Cylinder Life, How To Remove The Steam Cylinder, Figure #18

FAQ

How long does the cylinder last?

The cylinder can last anywhere from 500 to 2000 operating hours, as shown in Figure #16.

How do I remove the steam cylinder?

To remove the steam cylinder, follow the step-by-step guide under 'HOW TO REMOVE THE STEAM CYLINDER'.

How should I install the replacement cylinder?

To install a replacement cylinder, refer to the 'HOW TO INSTALL THE REPLACEMENT CYLINDER' section for detailed instructions.