technical data
Specification
Media Box Efficiency max. Maximum Face Velocity over Media
Maximum Face Velocity with Integral Mist Eliminator Pressure Drop at 500 fpm
Fire Protection Rating
Power supply pump (REflow, REflow C, REflow SC) Power consumption
Water supply pressure Unit Height
Unit Width
Unit Depth
Standards and guidelines
85% and 95%
750 fpm (3.8 m/s)
1080 fpm (5.5 m/s)
0.25IWC (62 Pa)
UL 900 Class I
120 VAC/1, 50 and 60 Hz
0.2- 0.6 kw 30 - 145 psi
26” (650mm) - 130” (3300mm) 24” (610mm) - 130” (3300mm) 30” (575mm)
UL 900 Class 1 and NRTL Approval
installation features & requirements
Only three connections to be made- water, drain and electrical
REflow pump model powered by a 120 V 1phase 60Hz connection
Stainless steel water tank and lateral supports
Media boxes can be installed in seconds
Footprint not to exceed 3” top and 2” side clearance from AHU/duct wall
performance
Efficiency (%)
Nortec MH Humidification Efficiency
100
90
80
70
60
50
100 | 200 | 300 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 | 1100 | |||
|
|
|
|
| Face Velocity (fpm) |
|
|
|
| ||||
|
| Media 8 inch depth |
|
|
|
| Media 12 inch depth |
| |||||
|
|
|
|
|
|
|
Nortec MH Pressure Drop
| 1.40 |
|
|
|
|
|
|
|
|
|
|
Drop (lWC) | 1.05 |
|
|
|
|
|
|
|
|
|
|
0.70 |
|
|
|
|
|
|
|
|
|
| |
Pressure | 0.35 |
|
|
|
|
|
|
|
|
|
|
| 0 |
|
|
|
|
|
|
|
|
|
|
| 100 | 200 | 300 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 | 1100 |
|
|
|
|
| Face Velocity (fpm) |
|
|
|
|
Media 8 inch depth Media 12 inch depth
Mist Eliminator 4 inch depth (necessary for velocity > 748 fpm) Mist Eliminator 8 inch depth (necessary for velocity > 885 fpm)