IMPSW180-01
PSW-180 SERIES
Differential Pressure Switches
I N S T R U C T I O N | ||
S H E E T | ||
| ||
|
|
GENERAL
The
Part I - Installation
Tools NeededScrewdriver to accommodate
Adjustable wrenches (2)
MOUNTING
LOCATE SWITCH WHERE VIBRATION, SHOCK, AND AMBIENT TEMPERATURE FLUCTUATIONS ARE MINIMAL. TO AVOID DAMAGE TO CONTROL, ALWAYS HOLD
THE WRENCH ON THE WRENCH FLATS OR HEX PORTION OF THE PRESSURE CONNECTION WHEN TIGHTENING.
The control can be mounted in any position. Locate where ambient temperature is above 30°F and below 160°F.
Surface MountingInsert two #6 screws through mounting ear holes on 2” centers (Recommended mounting for maximum vibration resistance).
Pipe MountingMount unit from its port(s). Always hold a wrench on pressure port when making pressure connection.
Making Pressure ConnectionUse a wrench on the pressure port and thread a 1/4” NPTM fitting into the port. Be sure to connect high pressure source to port labeled “HIGH”. Similarly, connect low pressure source to “LOW”.
NEVER TIGHTEN BY TURNING THE CONTROL INTO THE FITTING.
MODELS
WIRING
ALL LIVE SUPPLY CIRCUITS MUST BE DISCONNECTED BEFORE WIRING THE CONTROL. FOR ENCLOSED UNITS, CONNECT THE CONDUIT TO THE HOLE IN ACCORDANCE WITH NATIONAL AND LOCAL CODES. BRING WIRES UP TO THE TERMINALS FROM THE REAR. MAXIMUM RECOMMENDED
WIRE SIZE IS 16 AWG.Unscrew terminal just enough to put stripped wire under terminal block clamp.
Part II - Adjustments
Tools NeededScrewdriver
Use screwdriver to turn external adjusting screw on the side. Turn “in” (clockwise) to increase pressure setting. For best setting accuracy, set the switch using the actual working pressures encountered in the application.
Dimensions
MODEL | PORT | DIM A. |
DIFFERENTIAL |
|
|
PRESSURE |
|
|
1/4” NPSF |
| |
185, 186 | Polysulphone | 2.75” (69.9 mm) |
|
| |
184, 187, 188 | 1/4” NPTF Brass | 3.125” (79.4 mm) |