HIGH PERFORMANCE DIGITAL TYPE
TIME SWITCHES
TIME
SWITCHES (TB5)
FEATURES | APPLICATIONS |
DIN rail mount | Lighting Fixture |
DIN module size | Sign board |
15 minutes interval setting (Daily) | Factory facility |
2 hours interval setting (Weekly) | Vending machines |
Power supply indication LED lamp |
|
3 state terminal |
|
Metal setting pin |
|
| |
EN50178, DIN57633 conformed |
|
PRODUCT TYPES
Model No. | Product name | Rated voltage | Power failure backup | |
TB5560187 | Analogue type daily TIME SWITCH (with power failure backup) | 300 hours | ||
TB5630187 | Analogue type weekly TIME SWITCH (with power failure backup) | 300 hours | ||
TB5590185 | Analogue type daily TIME SWITCH | 230VAC | __ | |
__ | ||||
TB5640185 | Analogue type weekly TIME SWITCH | 230VAC | ||
|
DIMENSIONS
TB5560187
54 | 66,5 | |
61 | ||
| ||
| 44 | |
| POWER |
| 19 | 18 | 17 | 16 | 15 | 141 |
|
|
|
|
|
|
| 3 |
|
|
|
|
|
|
| 1 | 45 90 |
|
|
|
|
|
| 2 | |
| 4 |
|
|
|
| 1 | |
|
|
|
|
|
| 1 |
|
| 2 | 10 |
|
|
|
|
|
PIN | 1 | 15 |
|
|
|
|
|
2 | 3 |
|
| 6 | 7 |
| |
INSIDE |
| 4 | 5 |
|
| ||
NO- ON |
|
|
|
|
| ||
NC - OFF |
|
|
|
|
|
|
|
PRESENT |
|
|
|
|
|
|
|
TIME |
|
|
|
|
|
|
|
1 | 2 |
| 3 |
|
| 4 | 5 |
33
CIRCUIT DIAGRAM
TB6110187 <1 Circuit type>
M
~
1 2 3 4 5
POWER COM NO NC
SPECIFICATIONS
Model No.
Program Cycle
Driving Method
Rated Voltage
Allowable Operating Voltage
Rated Frequency
Power Consumption
Time Indication
Power Supply Indicator
Number of Circuit
Circuit Configuration
Contact Configuration
Manual ON/OFF
Switching Capacity
Resistive Load (cosø=1)
Inductive Load (cosø=0.6)
Setting System
Minimum Setting Unit
Minimum Setting Interval
Number of Operation
Running Reserve
Charging Time
Time Accuracy
Working Ambient Temparature
Working Ambient Humidity
Degree of Protection
Protection Class
Pollution Degree
Over Voltage Category
Wiring Terminal Capacity
Weight
Option Parts
TB5560187 | TB5630187 | TB5590185 | TB5640185 | |||
Daily Type | Weekly Type | Daily Type | Weekly Type | |||
Quartz motor | AC synchronous motor | |||||
|
| 230V AC | ||||
| ||||||
|
|
|
| 50Hz | ||
| 2W |
|
|
|
| 2W |
Daily dial | Weekly dial | Daily dial |
|
| Weekly dial | |
Green LED |
|
| Red LED | |||
|
|
|
| |||
Separated Circuit (NO | ||||||
Single Pole, |
|
| ):∝−gap |
with
250V AC 16A
250V AC 3A
15 minutes | 2 hours | 15 minutes | 2 hours |
15 minutes | 2 hours | 15 minutes | 2 hours |
96/Day | 84/Week | 96/Day | 84/Week |
300 hours at 20°C |
|
| |
| |||
about 72 hours |
| ||
±15 sec/month(at 25°C) | Same as AC frequency | ||
|
| ||
|
| ||
| IP 20 as per EN60529 |
| |
Class II as per | |||
|
| 2 |
|
|
| III |
|
| 1~2.5mm2 |
| |
| 160g | 160g |
|
| TB55603777 / Terminal Cover |
|
SAFETY INSTRUCTIONS
1.All operations serving transport, installation, commissioning, troubles- hooting and maintenance are to be carried out by skilled technical personnel in accordance with the relevant safety regulations and standards.
2.Avoid using the time switch except for the environment condition shown in specifications. Indoor use only.
3.Load capacity differs, depending on the type of load. (See specifications).
4.Protect the circuit with a fuse ir breaker at the power supply, in accor
ONS
dance with the relevant regulations.
5.Synchronous motor type (TB559 .TB564) are not provided with run- ning reserve function. When the time error occurs due to power failure, readjust the present time.
6.Make wiring connections, using isnulated wire (1,0 to 2,5 mm2). Flexible codes conductors 1,0 to 2,5mm2.
Fixed wiring conductors 1,5 to 2,5mm2.
7.After wiring, check that wiring connections are all correct.
05/2005 | 1 |
|