Paradox Hellas S.A CT-V900 manual 350mA/700mA Battery Charging Jumper, Introduction, DIP Switches

Models: CAA470A-EI02 CT-V900

1 2
Download 2 pages 11.15 Kb
Page 1
Image 1
Assign Address (1 and 2)

 

CAA470A-EI02

2-Door Expansion Module

PRINTED IN CANADA 07/2004

 

CA-A470-A

Instructions

780 Industriel Blvd., Saint-Eustache (Quebec) J7R 5V3

CANADA

Tel.: (450) 491-7444

Fax: (450)

491-2313

 

www.paradox.ca

 

Assign Address (1 and 2)

DIP switches 1 and 2 determine the 2-Door Expansion Module’s address in the network, regardless of the order that they are connected to the controller. Centaur recognizes the doors according to the DIP switch settings as shown in Figure 1.

Figure 1: Setting the network address

Access during Communication Failure (5 and 6)

DIP switches 5 and 6 determine the access to the protected doors during a communication failure.

Switch

Setting

During a Communication Failure:

 

 

 

 

 

5

= off (0)

“No Card”

 

6

= off (0)

Access is denied to all cards and doors

 

 

 

are locked until communication is restored.

 

5

= on (1)

“2 Cards”

 

6

= off (0)

Access is granted only when 2 cards of

 

 

 

a valid format are presented to the reader.

 

5

= off (0)

“All Cards”

 

6

= on (1)

Access is granted when any card with

 

 

 

a valid format is presented to the reader.

 

 

 

 

 

5

= on (1)

“Unlock Door”

 

6

= on (1)

Doors are unlocked until communication

 

 

 

is restored.

Figure 3: Setting the A+ and B- jumpers

Jumpers set to low

Jumpers set to high

 

A+ B-

 

A+ B-

 

 

 

 

LOW

 

 

 

 

LOW

 

 

 

 

HIGH

 

 

 

 

HIGH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

350mA/700mA Battery Charging Jumper

The 350mA/700mA Jumper allows you to select the charging current for the backup battery of the 2-Door Expansion Module. Charging the battery at 350mA takes longer, but consumes less power. Charging the battery at 700mA takes less time, but consumes more power.

Figure 4: Setting the 350mA/700mA jumper

Jumper set

Jumper set

as 350mA

as 700mA

Introduction

Connected to the CT-V900 controller’s expansion bus, the 2-Door Expansion Module (CA-A470-A) supports two readers, two BCD keypads, four zone inputs, 6 outputs and two locking devices.

Activate Output on Communication Failure (7)

DIP switch 7 determines if OUT5 and OUT6 will pulse during a communication failure. When DIP switch 7 placed in the ON position, the outputs on the device(s) connected to the OUT5 and OUT6 terminals will pulse. For example, the LED on the reader can pulse to advise users that a communication failure has occurred.

DIP Switch (8)

For future use.

Programming in Centaur

Using the Centaur Access Control Software, program the inputs, outputs, readers, and keypads connected to the 2- Door Expansion Module. The options are explained in the Centaur Access Control Software Reference Manual.

Centaur will identify the 2-Door Expansion Module by its address (see DIP Switches 1 to 4) and will recognize the devices as follows:

Specifications

CA-A470-A Specifications:

Readers:

connect 2 per module

Keypads:

connect 2 per module

Inputs:

4 standard without ATZ, 1 tamper

Outputs:

6 (open collector)

Lock Outputs:

2 lock outputs (Form C relays)

 

each: 15A @ 16VDC (resistive)

AC Power:

16VAC, 40VA max.

Frequency:

50Hz/60Hz

Aux. Current:

500mA (max.)

Battery:

12VDC, 7Ah

 

low battery = 10.2VDC

 

low battery restore = 12.2VDC

 

low battery cut-off = 8.5VDC

Communication: expansion bus (E-Bus), RS-485, Plug and Play, 3 modules per CT-V900

Operating temp.: 5oC to 55oC (41oF to 133oF)

DIP Switches

In order for new DIP switch settings to take effect, the 2-Door Expansion Module’s power must be disconnected and then reconnected.

Lock State during Communication Failure

DIP switches 3 and 4 determine the state of Lock #1 and Lock #2 ONLY during a communication failure between the 2-Door Expansion Module and the controller (CT-V900- A). Normally, the lock outputs follow the Lock Control for the CT-V900-A. Therefore, the DIP switches should have the same setting as the Lock Control for the corresponding doors in Centaur.

Lock #1 = DIP switch 3

Lock #2 = DIP switch 4

OFF = De-energized:

During a communication failure, the normal state of the lock output is De-energized. When Lock #1 or Lock #2 is activated, power is applied to the corresponding lock output to unlock the door. Activation depends on the setting of the DIP switches 5 & 6 (Access during Communication Failure).

ON = Energized:

During a communication failure, the normal state of the lock output is Energized. When Lock #1 or Lock #2 is activated, power is removed from the corresponding lock output to unlock the door. Activation depends on the setting of the DIP switches 5 & 6 (Access during Communication Failure).

De-energized: no power in normal state; requires power to activate.

Energized: power in normal state; remove power to activate.

EOL Jumper

Place the EOL jumper ON if the 2-Door Expansion Module is at the beginning (Start Point) or at the end (End Point) of the E-bus Network (see Figure 2). Otherwise, place the EOL jumper OFF.

Figure 2: Setting the Jumpers

High/Low Bias Jumpers

Place the A+ and B- jumpers on LOW only if the 2-Door Expansion Module is at the beginning (Start Point) of the E-bus Network. Otherwise, place the A+ and B- jumpers on HIGH (see Figure 2 and Figure 3).

 

Address 1

Address 2

Address 3

 

 

 

 

Doors

 

 

 

Keypad/Reader 1

Door 3

Door 5

Door 7

Keypad/Reader 2

Door 4

Door 6

Door 8

Inputs

 

 

 

Z1

Input 17

Input 21

Input 25

Z2

Input 18

Input 22

Input 26

Z3

Input 19

Input 23

Input 27

Z4

Input 20

Input 24

Input 28

Outputs

 

 

 

OUT1

Output 7

Output 13

Output 19

OUT2

Output 8

Output 14

Output 20

OUT3

Output 9

Output 15

Output 21

OUT4

Output 10

Output 16

Output 22

OUT5

Output 11

Output 17

Output 23

OUT6

Output 12

Output 18

Output 24

Doors cannot be defined as Door Type Elevator (Door Properties window, General tab, Door Type: Elevator) and the module does not support Interlock Inputs (Door Properties window, Inputs and Outputs tab, Interlock Input).

Other modules in the system cannot activate the 2- Door Expansion Module’s outputs.

The 2-Door Expansion Module does not support Zone Doubling (see Figure 6).

Page 1
Image 1
Paradox Hellas S.A CT-V900 manual 350mA/700mA Battery Charging Jumper, Introduction, Programming in Centaur, DIP Switches