CURRENT READING

TEMPERATURE

0°C

 

0°F

DEWPOINT

0°C

 

0°F

PRESSURE

0.0 PSIG

REFRESH

0.0 BAR

 

BACK

 

EXIT

 

ACK ACTION

Acknowledge action programs the alert label behavior after the alert condition has been acknowledged. The following settings are available for ACK ACTION:

ALWAYS ON - The alert label is displayed until alert conditions are cleared.

OFF 8 HRS - The alert label is turned off for 8 hours. Label returns after 8 hours if the alert condition persists.

OFF 24 HRS - The alert label is turned off for 24 hours. Label returns after 24 hours if the alert condition persists.

OFF 48 HRS - The alert label is turned off for 48 hours. Label returns after 48 hours if the alert condition persists.

ACTIVATE AUX

This setting activates an auxiliary when an alert condition exists. ACTIVATE AUX settings include the following:

NO (default) - Not activated.

1 - An alert condition will close AUX 1.

2 - An alert condition will close AUX 2.

CURRENT READING

The Current Reading menu displays the existing status of temperature, pressure, and dew point inside the dome system. An arrow displayed to the left of a menu item denotes that an alert condition exists.

An up arrow indicates the reading is over the threshold. A down arrow indicates the reading is below the threshold.

The high temperature alert occurs if the temperature is above 140°F (60°C). The low temperature alert occurs if the temperature is below -40°F (-40°C). The high pressure alert occurs if the pressure is above 11 PSIG.

The low pressure alert occurs if the pressure is below 1 PSIG.

The dew point (high humidity) alert occurs if the difference between the temperature and the dew point is less than or equal to 3°C.

Due to the heat emitted from the electronics of the camera, normal temperature operating range is approximately 95°F (35°C).

ALERT RESET

Alert reset clears the alert condition and removes the alert label from the monitor. The system automatically checks internal conditions 60 seconds after reset. If conditions are still unaccept- able, the alert label reappears on the screen indicating further corrective action is required.