[ 10 ] Pelco Manual C2915M-E (08/05)
Table B. Wiring Distances for 5 VA Cameras (24 VAC/12 VDC)
The following are the recommended maximum distances for low voltage cameras. These distances are calculated
with a 10 percent voltage drop. (Ten percent is generally the maximum allowable voltage drop for AC-powered
devices.)
EXAMPLE: A camera that requires 5 VA and is installed 224 feet (68 m) from the transformer would require
a minimum wire gauge of 24 AWG.
Wire Gauge 24 VAC 12 VDC
AWG mm2Feet Meters Feet Meters
24 0.25 224 68 56 17
22 0.35 356 108 89 27
20 0.5 567 172 141 42
18 1 902 274 225 68
16 1.5 1432 436 358 109
14 2.5 2285 696 571 174
12 4 3622 1103 905 275
10 6 5760 1755 1440 438