17.The pump motor must be wired for the proper voltage in accordance with the wiring diagram supplied with the motor. Wiring the motor with the incorrect supply voltage will cause damage to the motor and void the warranty.
18.The wiring to the motor should be kept as short as possible and large enough NOT to cause an excessive voltage drop. Use the wire size table as a guide in selecting minimum conductor size.
RECOMMENDED CIRCUIT BREAKER AND WIRING DATA
MOTOR | BRANCH | VOLTS | DIST. IN FT. OF BRANCH CIRCUIT | |
|
| |||
HP | CIRCUIT | Hz/PHASE | ||
|
|
| ||
|
|
|
|
|
3/4 | 15 A | 115/60/1 | #14 | #14 |
|
|
|
|
|
1 | 15 A | 115/60/1 | #12 | #12 |
|
|
|
|
|
20 A | 115/60/1 | #12 | #10 | |
|
|
|
|
|
15 A | 230/60/1 | #14 | #14 | |
|
|
|
|
|
MIN. SERVICE
WIRE
SIZE
TO MOTOR
19.Install, ground and bond wire according to local or National Electrical Code requirements.
GROUNDING
20.Permanently ground motor. Use green terminal provided under motor canopy or access plate; use size and type wire required by code. Connect motor ground terminal to electrical service ground. On cord connected circuits, check for proper grounding.
BONDING - (for permanently wired pumps)
21.The National Electrical Code Article
WARNING
(For cord and
WARNING
(For cord and
WARNING
(For cord and
CAUTION
Do not install within an outer enclosure or beneath the skirt of a hot tub or spa unless so marked.
P/N 350039 Rev. C | 5 |