Polycom DOC2557B Connecting the RMX 1500 to a Power Source, Connecting the RMX 1500 to AC Power

Models: DOC2557B

1 29
Download 29 pages 12.64 Kb
Page 11
Image 11

Polycom RMX 1500 Hardware Guide

Connecting the RMX 1500 to a Power Source

The following restrictions apply to the conductors and connectors that may be used to ground the unit when rack mounted:

When using bare conductors, they must be coated with an appropriate antioxidant compound before crimp connections are made. Tinned, solder-plated or silver-plated connectors do not have to be prepared in this manner.

The same bolt assemblies should not secure multiple connectors.

Listed fastening hardware must be compatible with the materials being joined and must be preclude loosening, deterioration and electrochemical corrosion of the hardware and joint materials.

Connecting the RMX 1500 to AC Power

Do not connect the green or green-yellow wire to the system single-point ground screw.

Only the AC Power cable supplied by Polycom should be used.

The size of the protective earthing conductor should be a minimum of 10AWG.

The outlet intended for connecting the power cord must be protected with an external overcurrent protection device either in building or in the rack with the rating not higher than 20Amp.

Do not use an Extension cord with the cable.

1 Make sure that the power button is switched OFF on the RMX 1500.

ON/OFF

button

USB Slot

2Insert the power cable into the power connector on the rear panel of the RMX 1500.

1-7

Page 11
Image 11
Polycom DOC2557B manual Connecting the RMX 1500 to a Power Source, Connecting the RMX 1500 to AC Power