Medical Package System

facing the black fan shroud and counterclockwise if facing the compressor flywheel.)

c.Set both selector switches to the auto position. Compressors will both run until the lead pressure switch closes.

d.Open valve at the air receiver leading to Medical Air System.

e. Check for air leaks at the connections.

9.Check that the compressor operates without excessive vibration, unusual noises or leaks.

10.Check the discharge pressure. Also make sure the air pressure rises to the designated pressure setting by checking the discharge pressure gauge.

11.Check the operation of the pressure switch or the pilot valve for continuous run units by opening the stop valve and confirming the compressor starts or reloads as pressure drops.

QUADPLEX MPQ

DUPLEX MPD

DRYER SYSTEM

FILTER SYSTEM

 

 

MDR OR MDD

MFP

++

TRIPLEX MPT

32"

32"

32"

8"

LEFT

Consult factory

 

RIGHT

END

 

END

for special voltages

 

VIEW

 

VIEW

or arrangements.

 

 

 

 

COMPRESSOR MAINTENANCE SCHEDULE

 

 

 

 

Operating Hours

 

 

 

Item

Action needed

500

2500

5000

10,000

15,000

20,000

Remarks

Tank

Drain moisture

Daily

2500

 

 

 

 

 

Inlet air filter

Replace

(Every 2,500 hrs or less)

 

 

Blower fan

Clean

 

 

 

Fan Duct

Clean

 

 

 

Compressor Fins

Clean

 

(Every 2,500 hrs or less)

 

 

Bearings

Replace

 

 

 

 

Compression rings

Replace

 

 

 

 

 

Wrist pin bearing

Regrease

 

 

 

 

 

Piston set

Replace

 

 

 

 

 

 

V-belt

Inspect, replace

*Note 3

 

Safety valve

Confirm operation

 

(Every 2,500 hrs or less)

 

 

Pressure gauge

Inspect

 

(Every 2,500 hrs or less)

 

 

 

 

 

 

 

 

 

 

 

Air leaks

Inspect

 

 

 

 

Filters

Replace

 

▲ (View delta pressure

Moisture drains

Inspect

 

 

indication)

 

 

 

 

traps

 

 

 

 

 

 

 

 

Suction pressure

 

 

 

(refrigerated)

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

Inspect ▲ Replace

1.Inspect and perform maintenance periodically according to maintenance schedule.

2.The maintenance schedule relates to the normal operating conditions. If the circumstances and load condition are adverse, shorten the cycle time and do maintenance accordingly.

3.* The tension of the V-belt should be adjusted during the initial stage and inspected every 1,500 hours afterwards. Proper belt tension for 3/4 to 3 HP units is 12 lbs./.5” deflection; for 5 to 20 HP units, 16 lbs./1.5” deflection

5