ALPHA 95 COMPONENT CHART
0 - 00J - W - 08 - 03 - IU - 12 - 00 - GG - F
Hardware
0 = None
T = Extractor Clips
Efficiency
00J = 95% DOP
Capacity/Pack Style
C = Separator
D = 4 inch Pureform
F = 8 inch Pureform
W = 11 inch Pureform
Frame Material
02 = 16 GA 409 Stainless
03 = 16 GA 304 Stainless
04 = 3/4 in. FIRE RETARDANT PLYWOOD
05 = FABRICATED ALUMINUM
07 = 3/4 in. FIRE RETARDANT PARTICLE BOARD
08 = 16 GA. GALVANNEAL
11 = 3/4 in. NON FIRE RETARDANT PARTICLE BOARD
16 or 17 =
24 GA. STEEL
Frame Style
00 = BOX
01 = SINGLE HEADER (13/16”)
02 = DOUBLE HEADER (13/16”)
03 = DOUBLE TURNED FLANGE
05 = 3/4 IN. DEEP CHANNEL GEL SEAL
08 =
Sealant Material
IU = URETHANE
IH = HOT MELT
Gasket material | Gasket location | ||
0 | = NONE | 0 | = NONE |
1 | = NEOPRENE | 1 | = UPSTREAM |
5 | = BLUE JEL | 2 | = DOWNSTREAM |
|
| 3 | = BOTH SIDES |
Filter Depth
D =
F =
Filter Face Size (HxW)
B = 8” N = 30” R = 60”
C = 12” P= 36” S = 72”
E = 18” H = 42” U =
G = 24” Q = 48” Y =
Odd Size Designator
Odd size designators are anAlpha Numeric description. The first two digits specify the height whole number with an alpha designator specifying the height fraction. The second two digitsspecifythewidthwholenumberwithanalphadesignator specifying the width fraction. And the last alpha designator specifies the depth. If the height or width is less than 10 inches, use a 0 in front of the dimension.
A = 0” | F = 5/16” | L= 5/8” |
B = | M = 11/16” | |
C = 1/8” | H = 7/16” | N = 3/4” |
D = 3/16” J = 1/2” | P = 13/16” | |
E = 1/4” | K = 9/16” | Q = 7/8” |
|
| R = 15/16” |
Faceguard Material | Faceguard Location | ||
0 = NONE | 0 | = NONE | |
1 | = GALVANIZED 4X4 MESH | 1 | = UPSTREAM |
G = ALUMINIZED EXPANDED METAL | 2 | = DOWNSTREAM | |
2 | = 17GA. SS 4X4 MESH |
|
|
5 | = 22 GA. SS 4X4 MESH |
|
|
Frame: Alpha 95 filters are available in a variety of wood and metal frame materials such as particle board, plywood, galvanized steel and stainless steel. Alpha 95 filters are also available in 24 gauge corrosion resistant steel in single or double headers for installation in side access or plenum applications.
Seal: The standard gasket seal is 0.75” x 0.25” neoprene for installation on either the upstream, downstream or both sides of the filter. The standard Fluid Seal is Flanders
Faceguards: Faceguards are used to protect the filter media from mechanical damage. The typical faceguard material is expanded aluminized steel. Galvanized 4 x 4 mesh welded wire and Type 304 stainless steel faceguards are also available.
UL: Alpha 95 filters are either UL900 Class 1 or Class 2 listed depending on materials of construction.
Banks: Alpha Frames are designed for Alpha 95 filters in