Nominal |
| Nominal | 250 fpm | 375 fpm | 500 fpm | 625 fpm | Media | Weight | |||||
Depth | Efficiency | Size |
|
|
|
|
|
|
|
| Area | Each | |
cfm | pd | cfm | pd | cfm | pd | cfm | pd | ||||||
(inch) |
| HxWxD | (sq.ft.) | (lbs.) | |||||||||
|
| (inch) |
|
|
|
|
|
|
|
|
|
| |
12 | 65% | 24x24x12 | 1000 | .20 | 1500 | .35 | 2000 | .45 | 2500 | .57 | 140 | 26 | |
24x12x12 | 500 | 750 | 1000 | 1250 | 69 | 14 | |||||||
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
12 | 95% | 24x24x12 | 1000 | .25 | 1500 | .45 | 2000 | .65 | 2500 | .78 | 140 | 27 | |
24x12x12 | 500 | 750 | 100 | 1250 | 69 | 14 | |||||||
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Notes:
1.PD represents clean pressure drop in inchw.g. The recommended final pressure drop is 1.5 inch w.g.
2.Operation down to zero velocity is satisfactory for all models.
3.Performance tolerances conform to section 7.4 of ARI Standard 850.
4.Performance values stated may be averages typical of the products listed. Contact factory for actual performance test reports on specific products.
5.Perfmormance values shown in this publication may be averages or estimates intended to generally represent product styles. Always contact factory for latest actual test data on specific Flanders Precisionaire models.
Guide Specifications
1.0 | General | 2.4 | |
1.1 | Medium and high efficiency gas turbine rigid fil- |
| guards shall be installed on the air entering and |
| leaving sides. | ||
| ters shall be PrecisionCell GT extended media |
| |
|
|
| |
| separator type filters as manufactured by | 2.5 | 1/2” |
| Flanders. |
| installed on the air leaving side and horizontal |
1.2 | Filter sizes, efficiencies and capacities shall be |
| strap on air entering side. |
|
| ||
| as scheduled on the drawings. | 2.6 | Filters shall be UL 900 Class 1 listed. |
2.0 | Filter Construction | 3.0 | Performance | |
2.1 | Filters shall be constructed by pleating a con- | 3.1 | Initial and final resistance shall not exceed the | |
| tinuous sheet of |
| scheduled values. | |
| 3.2 | Media area must equal or exceed that of the | ||
| spaced pleats with | |||
|
| specified filter. | ||
| aluminum separators. |
| ||
| 3.3 | The average efficiency shall be as determined | ||
2.2 | The filter pack shall be compression sealed into | |||
| by the ASHRAE Standard 52.1 and 52.2 test | |||
| a 24 ga. |
| ||
|
| methods. | ||
|
|
| ||
2.3 | The enclosing frame shall be assembled in a | 3.4 | The manufacturer shall guarantee performance | |
|
|
rigid manner and shall incorporate a single or | as stated in the literature within tolerances as | |
double header as required by job conditions. | ||
outlined in section 7.4 of ARI Standard 800. | ||
|
Flanders PrecisionAire
Foremost in Air Filtration
Toll Free:
REPRESENTED BY: