Precisionaire PB1403 dimensions Guide Specifications, Alpha Ht Component Chart

Models: PB1403

1 2
Download 2 pages 3.61 Kb
Page 2
Image 2
ALPHA HT COMPONENT CHART

ALPHA HT COMPONENT CHART

0 - 0 0 7 - C - 0 2 - 0 3 - I E - 3 2 - 0 0 - G G - F

Hardware

O = None

T = Extractor Clips

Efficiency

007 = 99.97% DOP

99.99% on .30 micrometers=SU Sealant

Capacity / Pack Style

C = Separator

Frame Material

02 = 16 GA 409 Stainless

03 = 16 GA 304 Stainless

Frame Style

03 = Double-Turned Flange

05 = 3/4 in. Deep Channel

Sealant Material

IE = High Temperature Silicone IG = Ceramic and Glass Mat

SE = high Temperature Silicone Scan Tested (99.99% on 0.30 micrometers)

Gasket Material

 

Gasket Location

 

 

 

0

= None

0

= None

3

= Silicone Sponge

1

= Upstream

4

= Woven Glass

2

= Downstream

5

= Blu Jel

3

= Both Sides

Filter Depth

D = 5-7/8

F = 11-1/2

Filter Face Size (H x W)

B=8” N=30” R=6

C=12” P=36” S=72”

E=18” H=42” U=113/8

G=24” Q=48” Y=23 3/8

ODD Size Designator

Odd size designators are an alpha numeric descrip- tion. The first two digits specify the height whole num- ber with an alpha designator specifying the height fraction. The second two digits specify the width whole number with an alpha designator specifying the width fraction. And the last alpha designator specifies the depth. If he height or width is less than 10 inches, use a 0 in front of the dimension.

A = O”

E=1/4”

J=1/2”

N=3/4”

B=1-1/16”

F=5/16”

K=9/16”

P=13/16”

C=1/8”

G=3/8”

L=5/8”

Q=7/8”

D=3/16”

H=7/16”

M=11/16”

R=15/16”

Faceguard Material

Faceguard Location

0

= None

 

0= None

G = Aluminized Expanded Metal

1

= Upstream

5

= 22GA.SS 4x4 Mesh

2

= Downstream

 

 

 

3

= Both

Guide Specifications

1.0

General

3.0 Performance

 

 

 

 

 

1.1

High temperature separator style HEPA filters shall

3.1 Initial and final

resistances shall not exceed the

 

be Alpha HT models as manufactured by Flanders.

 

scheduled values.

 

 

 

 

1.2

Filter sizes, capacities and construction options

3.2

Alpha HT HEPA Filters shall have a minimum effi-

 

shall be as scheduled on the drawings.

 

ciency of 99.97% on 0.30 micrometer particles when

2.0

Filter Construction

 

tested at rated capacity on a Q-107 Penetrometer in

2.1 The filter pack shall be constructed by pleating a

 

accordance with IEST-RP-CC-001.3, Type A.

Each

 

filter shall be challenged with an approved nearly

 

continuous sheet of non-woven water-resistant

 

 

 

monodispersed oil aerosol of 0.30 micrometer size.

 

fiberglass media around hemmed-edge corrugated

 

 

 

Measure the upstream and downstream concentra-

 

aluminum separators.

 

 

 

tion of these particles with a

light scattering

pho-

2.2

The filter pack shall be sealed into a (409 stainless

 

 

tometer, determine the penetration and calculate the

 

steel) (304 stainless steel) frame with a high tem-

 

 

 

efficiency.

 

 

 

 

 

 

perature silicone sealant rated for 500°F or a glass

 

 

 

 

 

 

 

3.3

Alpha HT Scan Tested HEPA Filters shall have

a

 

pack sealant rated for 1,000°F in exhaust applica-

 

 

minimum efficiency of 99.99% on0.30micrometer

 

tions.

 

 

 

particles when tested at rated capacity on a Q-107

2.3

(A chlorastic silicone gasket) (a woven glass gasket)

 

 

Penetrometer in

accordance

with IEST-RP-CC-

 

shall be provided to seal the filter in the mounting

 

 

 

001.3, Type C. The scan test shall consist of chal-

 

device (Gasket Seal). A silicone gel shall be provid-

 

 

 

lenging the filter

with a

high

concentration

of

an

 

ed in a channel on one side to seal the filter in the

 

 

 

approved oil aerosol or

PSL

Spheres. Utilizing

a

mounting device. filters with silicone gel have a max-

photometer or particle counter, the media pack and

imum service temperature of 390°F (Gel Seal)

the pack-to-frame seal shall be scanned to insure

 

 

that there are no leak greater than .01% of the

 

upstream concentration at 100 fpm face velocity.

®

Flanders Filters, Inc.

531 Flanders Filter Road

Washington, NC 27889

Phone: (252) 946-8081

Toll Free: (800) 637-2803

Fax: (252) 946-3425

REPRESENTED BY:

Website: www.flanderscorp.com

Page 2
Image 2
Precisionaire PB1403 dimensions Guide Specifications, Alpha Ht Component Chart