LOW NOx TURBOPOWER® • PACKAGED WATER HEATER

POLYSHIELD® POLYMER-LINED STORAGE TANK

TANK SERIES 225 GALLONS VERTICAL

MODEL

Recovery gph c

INPUT

Min. Inlet

SCAQMD Energy

Dimensions

 

Blower

Shipping

Flow Gas

(inches)

 

 

Motor

Weight

 

 

 

 

NUMBER

40° - 120°F

40° - 140°F

Btu/h

Pressure

Model No.

A

B

 

C

HP

 

Amps

#

 

 

" W.C. d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000 P 225A-TPL

1000

800

800,000

4.5

8TPL

800 MBtu/h

44

8

 

1

1/2

 

7

1540

cRecoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss. d With standard gas train

* The information presented is for natural gas 0.6 S.G. Dimensions are in inches unless otherwise specified.

For standard and optional equipment, see form #PV 6453.

STANDARD GAS PRESSURE REQUIREMENTS:

SEE TABLE FOR MINIMUM PRESSURE BY MODEL. MAXIMUM STATIC INLET GAS PRESSURE IS 10.5" W.C.

FOR GAS PRESSURES OUTSIDE OF THIS RANGE,

CONTACT YOUR PVI REPRESENTATIVE.

VENTING REQUIREMENTS:

-.02" TO -.06" W.C. (NEGATIVE PRESSURE).

TYPE B VENTING.

ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY. CHECK NATIONAL FUEL GAS CODE UNDER "FAN ASSISTED."

STANDARD ELECTRICAL REQUIREMENTS:

VOLTAGE: 120V, 1Ø, 60 HZ., 20 AMPS.

OTHER VOLTAGES REQUIRE AN EXTERNAL

STEPDOWN TRANSFORMER.

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND SPECIFICATION WITHOUT NOTICE.

Product is patented in the U.S., Canada, and Mexico.

 

PVI INDUSTRIES, LLC

PV 6513 02/25/04

FORT WORTH, TEXAS 76111

(800) 784-8326 www.pvi.com

Page 1
Image 1
PVI Industries 1000 P 225A-TPL dimensions Standard GAS Pressure Requirements, Venting Requirements