DURAWATT EXR WATER HEATER
ELECTRICAL CONNECTIONS
1.Check rating plate on water heater for correct voltage, phase and amperage. Refer to wiring diagram for control component identification.
2.Use a proper wire size and branch circuit protection as required by the National Electrical Code and state/local codes. PVI electric water heater specification sheets show number and size of power connectors furnished with the heater for a minimum 90°C copper connecting wire.
3.Use correct size ground wire; attach to pressure connector marked “GR” inside the control enclosure.
4.Connect supply feeders to distribution block inside the control enclosure. Conduit openings have been provided for electrical connection and remote alarm circuitry as required. All holes should be sealed with appropriate threaded hole plug if not used.
5.A float type low water
STARTUP
1.Secure and
2.Check components to assure secure fit during transport and installation. Check wiring connections in junction box for full contact and tight connection.
3.Inspect conduit seals between the control enclosure and heating element junction boxes to ensure that they have been sealed.
4.Plumb water connections with appropriate shutoff valves, expansion tanks and check valves per local plumbing codes.
5.With water outlet valve closed, open relief valve and water inlet valve, and fill tank with water before turning on electricity. Dry energizing water heater immersion elements will burn out elements rapidly and void the element warranty. When water exits relief valve, close relief valve and continue to fill until tank is full.
6.Energize the main power circuit. Check power distribution to circuits with electrical meter to assure proper power supply and operation. If improper readings are indicated,
7.To set the operating thermostat, remove the heating element junction box screw cover. (The thermostat is located in one element housing only - check upper element first for thermostat location.) A dial type thermostat has been selected for ease of use. Align desired temperature (°F) with element temperature indicator mark and secure cover.
NOTE: The mercury displacement contactors are activated by a magnetic field and will make some noise and vibration. This is normal.
3 | Section 33 |