25Quadra-fire • QV32B-A, QV36B-A • 2014-900 Rev. F • 9/06
Figure 18. Venting with three 90° elbowsUse SL D-Series
components only.H
1
H
V
1
V
NOTE: There MUST be a 25% reduction in total H when
using flex vent except when using the simple up and
out installation (see Figure 9).
VENTING WITH THREE (3) 90o ELBOWS
NATURAL GAS VENTING WITH THREE (3) 90o ELBOWS
PROPANE
V + H + V1 + H1 MAX. = 40 FT (12.2m) V + H + V1 + H1 MAX. = 40 FT (12.2m)
V (MIN.) H (MAX.) H + H
1
(MAX.)
90
o
Elbow on Top 2 FT (610mm) 4 FT (1.22m)
1 FT (305mm) 3 FT (914mm) 6 FT (1.86m)
2 FT (610mm) 4 FT (1.22m) 8 FT (2.48m)
3 FT (914mm) 6 FT (1.86m) 12 FT (3.72m)
4 FT (1.22m) 8 FT (2.48m) 16 FT (4.8m)
5 FT (1.52m) 16 FT (4.8m) 16 FT (4.8m)
V (MIN.) H (MAX.) H + H
1
(MAX.)
90
o
Elbow on Top NOT ALLOWED NOT ALLOWED
1 FT (305mm) 2 FT (610mm) 4 FT (1.22m)
2 FT (610mm) 4 FT (1.22m) 8 FT (2.48m)
3 FT (914mm) 6 FT (1.86m) 12 FT (3.72m)
4 FT (1.22m) 8 FT (2.48m) 16 FT (4.8m)
5 FT (1.52m) 16 FT (4.8m) 16 FT (4.8m)