Raypak warranty Raytherm - Type H, Hydronic Heating Boilers, Models 181-401- Indoor, Engineer

Models: 181-401

1 2
Download 2 pages 11.27 Kb
Page 1
Image 1
Raytherm® - Type H

Job:

 

 

 

 

 

 

 

 

Raytherm® - Type H

Engineer:

 

 

 

 

 

 

Low NOx

 

 

 

 

 

 

Contractor:

 

 

 

 

 

Hydronic Heating Boilers

Prepared By:

 

Date:

 

 

 

 

 

Models 181-401 - Indoor

Model:

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW NOx

Less than 40 nanograms per joule

EFFICIENT

82% efficiency – highest of any atmospheric boiler available today

THERMAL SHOCK PROOF

Twenty-year warranty against thermal shock damage up to 150°F differential

Maximum operating temperature: 230°F

LIGHTWEIGHT

A floor load of 70 lbs./sq. ft. or less

HIGH RECOVERY

Cuts fuel costs substantially because the standby and radiation losses normal to other boilers and tank-type water heaters are eliminated

LOW WATER OPERATING TEMPERATURE Operates with water temperature as low as 105°F without condensing

Heat Exchanger

ƒASME Inspected and Stamped 160 PSIG

ƒNational Board Approved

ƒHeaders

Engineer: Cast Iron Glass-lined – Standard

Contractor: Bronze – Option A-1

ƒFinned Tubing

Hydronic Heating Boilers Copper – Standard

Prepared By: Cupro Nickel – Option A-3

ƒASME Steel Tube Sheet

ƒSilicone O-Rings

ƒASME Pressure Relief Valve

Date:Models 181-401 - Indoor 45 PSIG – Standard

PSIG ASME – Optional

ƒTemperature and Pressure Gauge, Shipped Loose

ƒWater Connections

Model: Left Hand – Standard

Indoor Right Hand – Option A-6

ƒFlow Configuration – Two-pass

ƒPump – Optional

Manual background Mounted, 1/8 HP, 120 V, 1, 60 Hz

Controls

ƒ120V, 60Hz, 1 Ph Power Supply

ƒ120/24V Transformer

ƒ100% Pilot Shut-off/Lockout

ƒElectronic, Intermittent Ignition (IID) Pilot

Controls (cont'd)

Temperature Controls

ƒ High Limit Control, Manual Reset

B-6

2-stage Aquastat –

ƒ

On/Off Switch

 

100-200ºF

ƒ

Flow Switch

B-26

2-stage Digital Controller

ƒ Economaster II Pump Time Delay

B-27

2-stage Digital Controller,

Gas Train

 

Outdoor Reset

Y-241

Electronic Sequencer,

ƒ

Natural Gas

 

1-4 Stages

ƒ Manual Main Gas Shut-off Cock

Y-281

Electronic Sequencer,

ƒ Main Gas Pressure Regulator

 

1-8 Stages

ƒ Redundant Safety Shut-off Valve

Additional Safety Controls

ƒ

Control Valve

ƒ

Firing Mode

F-10

Low Water Cut-off Probe

 

On/off (H4)

I-1

High Limit Control, Auto

 

Two-stage firing (H3)

 

Reset

ƒ

Design Certified

S-1

Low Gas Pressure Switch

 

ANSI Z21.13 H Stamp

S-2

High Gas Pressure Switch

Construction

ƒFront Controls

ƒ

Stainless Steel, Fan-Assisted

Regulatory Agency Requirements

 

Burners

 

 

ƒ

Polytuf Powder Coat Finish

 

 

ƒDraft Diverter

ƒBase – Optional

Manual background Combustible Floor Shield – Option J-1

Catalog No.: 2000.203E

Effective: 12-1-07

Replaces: 4-1-05

Page 1
Image 1
Raypak warranty Raytherm - Type H, Hydronic Heating Boilers, Models 181-401- Indoor, Engineer, Contractor, Prepared By