Raytherm - Type WH
Models 2100-4100
Model
MODELS WH 2100 – 4001 |
Model | MBTUH | Width | Overall | Gas | Water | Flue | Approx. | ||
Height | Conn. | Conn. | Dia. | Shipping | |||||
No. |
|
|
| ||||||
Input | Output | A | B | G | H | K | Weight (lbs) | ||
| |||||||||
2100 | 1722 | 61 | * | 3 | 24 | 1400 | |||
2499 | 2049 | 70 | * | 3 | 26 | 1580 | |||
3000 | 2460 | 2 | 3 | 28 | 1750 | ||||
3500 | 2870 | 2 | 3 | 30 | 1920 | ||||
4000 | 3280 | 2 | 3 | 32 | 2100 |
*
NOTES: Dimensions are in inches.
Ratings are for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings 4% for every 1,000 feet above sea level.
Models | Electrical Rating | ||
|
| ||
W/Pump | W/O | ||
| |||
| Pump | ||
|
| ||
| 951276 |
| |
| pump* | < 8 Amp | |
2100- | 11 Amps @ | ||
230VAC | @ | ||
4001 | |||
| 120VAC | ||
| 22 Amps @ | ||
|
| ||
| 110VAC |
| |
|
|
|
*Pump requires separate power supply
HEATER RATES OF FLOW AND PRESSURE DROPS
Model | 20°F ΔT | 30°F ΔT | 40°F ΔT | |||
No. | GPM | ΔP (ft) | GPM | ΔP (ft) | GPM | ΔP (ft) |
172 | 11.0 | 115 | 4.9 | N/A | N/A | |
N/A | N/A | 137 | 7.5 | 102 | 4.3 | |
N/A | N/A | 164 | 11.2 | 123 | 6.5 | |
N/A | N/A | 191 | 16.8 | 144 | 9.3 | |
N/A | N/A | N/A | N/A | 164 | 12.8 |
HEATER RECOVERY RATES (GPH)
Model |
|
| Temperature Rise |
|
| ||
No. | 20°F | 30°F | 40°F | 50°F | 60°F | 80°F | 100°F |
10336 | 6890 | 5168 | 4134 | 3445 | 2584 | 2067 | |
12300 | 8200 | 6150 | 4920 | 4100 | 3075 | 2460 | |
14765 | 9844 | 7383 | 5906 | 4922 | 3691 | 2953 | |
17227 | 11484 | 8613 | 6891 | 5742 | 4301 | 3445 | |
19688 | 13125 | 9844 | 7875 | 6563 | 4922 | 3938 |
Maximum acceptable flow through heat exchanger tubes is 200 GPM.
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805)
Catalog No.: 3500.24C | Effective: | Replaces: |