tom portion of a vertical tank and on the end of a hori- zontal tank.

To clean the tank, follow these steps:

1.Turn off the electricity and gas supply to the water heater piped to the storage tank.

2.Turn off electrical power to the circulating pump.

3.Close the valves on the hot water outlet on the top of the storage tank and the cold water supply to the system.

4.Ensure that the drain located on the bottom of the tank is routed to a floor drain with adequate capac- ity to allow the tank to be drained.

5.Open the drain valve and open a vent to allow the air to enter the tank (manually opening the relief valve will usually accomplish this). Use extreme caution, as the water exiting the tank drain may be very hot. Avoid contact with the hot discharge water to prevent the risk of severe scald injury.

6.Allow the tank to drain completely.

7.Remove the cover over the manway or hand hole (if equipped). Remove the bolt(s) securing the tank access opening. Use a flashlight to observe the sediment collected in the tank.

8.Use hand tools to remove all sediment from the in- terior of the tank. Use care not to damage the inte- rior lining of the storage tank.

9.Use a water hose to flush the remaining sediment from the interior surfaces of the tank and ensure that all debris is removed. Scale or sediment al- lowed to reach the potable system can foul valves, pumps, strainers and other water fixtures. Ensure that the tank interior is clean before refilling the ves- sel.

10.Install a new gasket on the manway or hand hole to prevent any possible leaks. Tighten the gasket properly to prevent leaks. Caution: Over tightening can result in cutting the gasket and allowing a water leak to occur.

11.Close the drain and open the cold water supply and hot water outlet. If the relief valve was used for a vent, ensure that it is now closed. Open the closest hot water valve to allow the air in the tank to vent as water enters the vessel. Close the valve opened for a vent when water flows from the valve.

12.Check the manway or hand hole and all related pip- ing for any water leaks.

13.Turn on electric power to the water heater and cir- culating pump.

14.Turn on the gas supply to water heater.

15.Observe heater and piping to ensure all compo- nents are functioning properly.

Magnesium Anode Rod

Inspection

Glass lined storage tanks have magnesium anodes to cathodically protect the lining and minimize corrosion. Aggressive water conditions in some areas of the coun- try may accelerate the deterioration of the anodes. The anodes should be periodically removed and inspected to determine if replacement is necessary.

The tank must be valved off from the system and fully drained to remove an anode for inspection. Raypak storage tanks have multiple anodes installed in threaded tappings along the length of the tank or on top of the tank. Adequate service clearance is required to allow removal of an anode. The anodes should be re- placed when more than six inches of the core wire is exposed at either end of the rod.

Dielectric Protection

Inspect each dielectric coupling at each tank connec- tion for corrosion and proper operation. This is done when the tank is empty using an Ohm meter, which must indicate there is no continuity between the tank and the system piping. Should the electrical isolation between the tank and its piping or structure fail, elec- trolysis will occur and the resulting damage will eventu- ally destroy the tank. This check must be repeated at least every 18 months with no water in the tank to en- sure proper operation of the dielectrics. Clean or re- place dielectric fittings as required.

Immersion Heating Coil

If the tank has a coil, it should be removed every twelve months for inspection to determine lime build-up on copper tubes. If build-up is excessive, the coil should be cleaned by immersion in 20% inhibited muriatic acid solution.

NOTE: For the sake of convenience, it is suggested that the Magnesium Anode Rod Inspection and the Dielectric Protection procedure be handled at the time of the yearly tank draining for cleaning pur- poses.

www.raypak.com

Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468 Litho in U.S.A.

Page 2
Image 2
Raypak 241355 warranty Magnesium Anode Rod Inspection, Dielectric Protection, Immersion Heating Coil

241355 specifications

The Raypak 241355 is a highly efficient, gas-fired heater designed for residential and commercial pool and spa applications. Known for its advanced technology and robust construction, it is a popular choice among pool owners seeking reliability and performance.

One of the standout features of the Raypak 241355 is its exceptional energy efficiency. It boasts a high thermal efficiency rating, thanks to its innovative design that maximizes heat transfer. This efficiency not only helps in reducing energy costs but also contributes to a smaller carbon footprint, making it an environmentally friendly option.

The unit is equipped with Raypak's exclusive Digital Control System, which allows for precise temperature adjustments and monitoring. This user-friendly interface features easy-to-read digital display controls, enabling users to set and maintain their desired temperature with accuracy. The integrated diagnostic system also provides real-time feedback, ensuring the heater operates smoothly and efficiently.

Another significant characteristic of the Raypak 241355 is its robust construction. The heater features all-copper heat exchangers that ensure durability and longevity, capable of withstanding chlorine and other corrosive elements often found in pool environments. The specially designed cabinet is corrosion-resistant, providing additional protection against the elements, which adds to the unit's overall lifespan.

Operating with natural gas or propane, the Raypak 241355 is versatile and can easily adapt to various energy sources. Its compact design allows for easy installation, whether in a new pool setup or as a replacement for an older model. The heater is also equipped with advanced safety features, including a built-in pressure switch and a venturi system that ensures safe operation.

In terms of performance, the Raypak 241355 offers rapid heating capabilities, making it ideal for quick pool parties or spontaneous swims. Its heating capacity is well-suited for medium to large-sized pools, ensuring a comfortable swimming experience regardless of outdoor temperatures.

In summary, the Raypak 241355 is an excellent investment for any pool owner looking for reliability, efficiency, and advanced technology. With its impressive features and durable build, it stands out as a premier choice in the competitive market of pool heaters, ensuring that users enjoy a warm and inviting swimming environment all season long.