Hi Delta FlexGas – Type H
Models 992BD-2342BD
Model
NOTE: Pump location varies based on model and application
RATES OF FLOW AND PRESSURE DROPS
Model |
| 20°F ∆T | 30°F ∆T | Min. Flow |
| Max. Flow |
| ||||||
| GPM | ∆P (ft) | GPM | ∆P (ft) | GPM | ∆P (ft) |
| ∆T | GPM | ∆P (ft) |
| ∆T | |
992BD |
| 84 | 5.6 | 56 | 2.5 | 42 | 1.5 |
| 40 | 132 | 14.0 |
| 13 |
1262BD |
| 107 | 10.0 | 71 | 4.5 | 53 | 2.6 |
| 40 | 132 | 15.5 |
| 16 |
1532BD |
| 130 | 16.0 | 86 | 7.1 | 65 | 4.1 |
| 40 | 132 | 16.5 |
| 20 |
1802BD | N/A | N/A | 102 | 10.8 | 76 | 6.0 |
| 40 | 132 | 18.0 |
| 23 | |
2002BD | N/A | N/A | 113 | 14.0 | 85 | 8.1 |
| 40 | 132 | 19.5 |
| 26 | |
2072BD | N/A | N/A | 117 | 15.0 | 88 | 8.7 |
| 40 | 132 | 19.5 |
| 27 | |
2342BD |
| N/A | N/A | 132 | 21.0 | 99 | 12.0 |
| 40 | 132 | 21.0 |
| 30 |
Basis is 30 GPM or 40°F ∆T for minimum flow, 132 GPM for maximum flow.
SPECIFICATIONS
|
|
|
|
|
|
|
|
|
|
| Approx. |
| MBTUH | Firing | A | B | H | K | T | W | Amp. | Shipping | |
Model | Input | Output | Stages | Width |
| NPT |
|
|
| Draw* | Wt. (Lbs.) |
992BD | 990 | 832 | 3 | 10 | 10 | <12 | 930 | ||||
1262BD | 1260 | 1058 | 4 | 12 | 10 | <12 | 1040 | ||||
1532BD | 1530 | 1285 | 4 | 36 | 12 | 10 | <12 | 1255 | |||
1802BD | 1800 | 1512 | 4 | 14 | 10 | <12 | 1380 | ||||
2002BD | 1999 | 1679 | 4 | 39 | 14 | 10 | <12 | 1480 | |||
2072BD | 2070 | 1739 | 4 | 39 | 14 | 10 | <12 | 1480 | |||
2342BD | 2340 | 1966 | 4 | 34 | 16 | 10 | <12 | 1550 |
* Without pump
NOTES:
1.Dimensions are in inches.
2.Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installation above 5,000 feet, please contact manufacturer.
3.Required natural gas supply pressure is
7 - 10.5” WC. Required propane gas supply pressure is 11 - 13” WC.
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805)
Catalog No.: 2000.313A | Effective: | Replaces: |