Job: |
|
|
|
|
| TempTracker™ | |
|
|
|
|
| |||
Engineer: |
| 2- and | |||||
Contractor: |
| ||||||
For Hi Delta® and Raytherm® | |||||||
Prepared By: |
| ||||||
Date: | Boilers & Water Heaters | ||||||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
TempTracker is designed to sequence multiple boilers up to four total stages, whether it’s one to four on/off boilers, two
Features
•
•Selectable P or PID logic
•LCD display
•NEMA 1 enclosure
•
•System water sensor
•Outdoor air sensor (Models
•Alarm ready (pilot duty)
•24 VAC, 60 Hz, 3 VA Supply Power
•Relay Ratings
Stage 1: 5A @ 120 VAC
Stages 2 to 4: 3A @ 120 VAC
Programmable Functions
•6 programming modes
•Adjustable outdoor reset
•Min. system water temperature (70 °F)
•Max. system water temperature o Heating – 220 °F
o DHW – 190 °F
•Temperature differential (2 to 42 °F)
•Boiler target (70 to 220 °F)
•Outdoor cutoff (35 to 85 °F)
•Boiler mass (low, med, high)
•
(10 sec. to 8 min.)
•System
•Temperature measurement (°F or °C)
Model Information
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805)
Catalog No.: 5100.30A | Effective: | Replaces: |