T-3 Modbus Interface
Interface Board
Certified Modbus Compatibility ProSoft Series 1500 Translator
Read/Write Attributes
Analog/Binary
Total B6000 BMS Program Access
Data Integrity Protocol
Summation/Modulus Error Checking
Auto Command Error Feedback
LED Diagnostic Indicators
Port 1 Active − Green
Port 2 Active − Green
Port 1 Error − Red
Port 2 Error − Red
Electrical Characteristics
120 VAC, 0.25A, 60 Hz
Ambient Conditions
Temperature:
Humidity: | 90% RH |
Enclosure
Heavy Gauge Steel Lockable Access Door Tamper Resistant Design 15 3/16L x 8 W x 4 3/4D Boiler or Remote Mounted
Limited One Year Warranty
U® L
Sample Specification
Section I: General Requirements
1.Provide a Raypak
2.The interface shall be microprocessor based.
3.The interface shall be UL Listed.
4.The interface shall carry a one year limited warranty against failure caused by defective workmanship or material.
5.The interface and boiler control system shall be manufactured by the same company and shall carry single source responsibility.
Section II: Equipment Enclosure
1.The interface enclosure shall be constructed of heavy gauge steel and shall be protected with a
2.The front access door of the interface enclosure shall be lockable and the enclosure shall be tamper resistant.
Section III: Control Functions
1.The interface shall provide seamless communications integration between the Raypak B6000
2.The interface shall utilize summation/modulus error checking and auto command error feedback to ensure data integrity.
3.The interface shall allow analog and binary
a)Reset parameters including: Setpoint, Reset Ratio, Temperature Rise and Control Band.
b)Outdoor cutoff parameters including: Outdoor Cutoff Temperature and Outdoor Cutoff Deadband.
c)Secondary operating parameters including: Firing Step Increment, Pump
d)Setback parameters including: Setback Period Scheduling and Setback Activation.
e)
Section IV: Display Functions
1.The interface shall have port active and error diagnostic lights for both interface ports.
2.The interface shall allow analog and binary
a)Current temperatures including: Water Temperature, Outdoor Air Temperature, and Target Temperature.
b)Boiler operating status including: Valve Position, and Current Firing Rate.
c)Fault indication including: Low Water, Low Gas Pressure, High Gas Pressure, High Temp, Low Water Pressure, Low Flow, No Pilot and Manual Override Status.
d)Secondary operating parameters including: Time Remaining Till Lead Boiler Rotation and Valve Operating Times.