Regency Liberty L900 Gas Fireplace
L900-1 Gas Fireplace
Clearance Requirements:
Finished Floor | Vertical Terminations: |
The maximum height that combustible floor can be brought above the base of the unit is 3".
IMPORTANT NOTE
Combustible material can only be installed to the bottom lip of the fireplace as shown below. The finished floor must not come in contact with the front face of the fireplace.
Clearance: | Dimension | Measured From: |
A: Mantel Height | Minimum | |
B: Sidewall | Side of fireplace opening | |
C: Ceiling | 49” (1245mm) | Top of fireplace opening |
D: Mantel Depth | 13” (330mm) | Maximum |
E: Alcove Width | 84” (2134mm) | Sidewall to Sidewall (Minimum) |
F: Alcove Depth | 36” (914mm) | Front to back wall (Maximum) |
Combustible Mantels
Because of the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of the louvers are shown in the diagram below. Mantel may be installed anywhere in the shaded area or higher.
Mantel Clearances |
| Mantel | From Top of |
| |
14 12 10 8 | 6 4 2 0 |
| Clearances | Fireplace Opening |
|
13" (330mm) |
| A |
| ||
25 |
|
|
|
|
|
|
| Drywall | B |
| |
20 | 3 ½" (89mm) |
| C |
| |
| Header |
| |||
1" (25mm) | (On Edge) |
|
|
| |
|
|
| Horizontal Terminations: | ||
15 |
| D | |||
|
| ||||
|
| Facing |
|
|
|
10 | D | Standoff | Note: |
|
|
B |
|
|
|
| |
| C |
| A |
| |
|
|
|
| ||
|
|
| be installed at a lower height if |
| |
|
|
| the framing is made of metal |
| |
0 | Top of |
| studs covered with a |
| |
A |
| bustible board. |
| ||
Fireplace |
|
| |||
To Floor | Opening |
| Ensure the paint that is used |
| |
|
|
| |||
|
|
|
| ||
|
|
| on the mantel and the facing is |
| |
|
|
| “heat resistant” or the paint may |
| |
|
|
| discolour. |
|
|
Mantel Leg |
|
|
|
| |
Clearances |
|
|
|
| |
Combustible mantel leg |
|
|
| ||
clearances as per diagram. |
|
|
|
Clearances are from the finished edge of the fireplace opening.