This'water'heater'is'certified'for'installations'
up'to'3,280'feet'(1000'm)'above'sea'level.'
The'input'rating'of'this'water'heater'is'based'
on'sea'level'operation.'At'higher'elevations,'
the'actual'input'rate'may'be'lower'than'the'
value'listed'on'the'rating'label.
NOTICE:$For$installations$above$3,280$
feet$(1,000$m)$elevation,$contact$a$quaili`
fied$service$technician$to$make$the$proper$
altitude$adjustment.$$See$page$35$for$ad`
ditional$information.
Do$not$install$this$water$heater$at$eleva`
tions$above$3,280$feet$(1,000$m)$without$
the$proper$adjustement.$Please$contact$
your$installer,$local$gas$supplier,$place$of$
purchase$or$the$Customer$Service$phone$
number$as$listed$in$this$Use$&$Care$Manu`
al$for$more$information.$$
High$Altitude
Installing$the$Main$Remote$Control:
WARNING:$Do$not$attempt$to$convert$this$water$heater$for$use$with$a$different$type$of$gas$other$than$ the$type$shown$
on$the$rating$plate.$Such$conversion$could$result$in$hazardous$operating$ conditions.
Gas$Supply
The'supplied'Manual'Gas'Appliance'Shutoff'
Valve'must'be'installed'at'the'gas'connection'of'
the'water'heater'at'the'time'of'installation'(see'
diagram'to'the'left).
The'branch'gas'supply'line'to'the'water'heater'
should'be'a'minimum'of'3/4”'black'steel'pipe'
or'other'approved'gas'piping'material.
A'ground'joint'union'or'ANSI'design'certified'
semiErigid'or'flexible'gas'appliance'connector'
should'be'installed'in'the'gas'line'close'to'the'
water'heater.'The'National'Fuel'Gas'Code'
(NFGC)'ANSI'Z223.1'and'CAN'B149'code'
mandates'a'manual'gas'shutEoff'valve:'See'
NFGC'&'B149'for'complete'instructions.
If'flexible'connectors'are'used,'the'maximum'
length'shall'not'exceed'36”'(91'cm).
If'lever'type'gas'shut'offs'are'used,'they'shall'
be'approved'/'certified'gas'cocks.
Compound'used'on'the'threaded'joints'of'the'
gas'piping'must'be'of'the'type'resistant'to'the'
action'of'LP'gas.'Use'compound'sparingly'on'
male'threads'only.'
A'sediment'trap'should'be'installed'at'the'
bottom'of'the'gas'line.
Do'not'use'excessive'force'(over'31.5'ft'lbs.'
[42.7'Nm])'in'tightening'the'pipe,'particularly'if'
teflon'pipe'compound'is'used,'as'the'unit'may'
be'damaged.
The'inlet'gas'pressure'to'the'water'heater'must'
not'exceed'10.5”'w.c.'(2.6'kPa)'for'natural'or'
14”'w.c.'(3.5'kPa)'for'LP'gas.'For'purposes''
of'input'adjustment,'the'minimum'inlet'gas'
pressure'(with'main'burner'on)'is'shown'on'
the'water'heater'rating'plate.'If'high'or'low'gas'
pressures'are'present,'contact'your'gas'supplier'
for'correction.
NOTICE:'To'ensure'proper'operation'of'the'
heater'the'gas'pipe'and'gas'meter'must'be'sized'
correctly.
Gas'piping'shall'be'in'accordance'with'local,'
utility'company'requirement'and/or'in'the''
absence'of'local'codes,'use'the'latest'edition'of'
the'National'Fuel'Gas'Code.'In'Canada,'the'latest'
edition'of'CSA'B149.1'Natural'Gas'and'Propane'
installation'code.
Manual
Gas
Supply
Line
Shutoff
Manual Gas
Appliance
Shutoff
Union
Sediment Trap
Cap
(Valve)
(Supplied)
Leak$Testing
The'water'heater'and'its'gas'connections'must'
be'leak'tested'at'normal'operating'pressures'
before'it'is'placed'in'operation.
$$'Turn'on'the'gas'shutEoff'valve(s)'to'the'
water'heater.
$$$Use'a'soapy'water'solution'to'test'for'
leaks'at'all'connections'and'fittings.'
Bubbles'indicate'a'gas'leak'that'must''
be'corrected.$
The'factory'connections'should'also'be'leak'
tested'after'the'water'heater'is'placed'in'
operation.
WARNING:$Never$use$
an$open$flame$to$test$for$
gas$leaks,$as$property$
damage,$personal$injury,$$
or$death$could$result.
Pressure$Testing$the$Gas$Supply$System
The'water'heater'and'its'manual'gas'shutE
off'valve'must'be'disconnected'from'the'gas'
supply'piping'system'during'any'pressure'
testing'of'the'system'at'pressures'in'excess''
of'1/2'psi'(14”'w.c.'[3.5'kPa]).
The'water'heater'must'be'isolated'from'the'
gas'piping'system'by'closing'the'manual'gas'
shutEoff'valve'during'any'pressure'testing'of'
the'gas'supply'piping'at'pressures'equal'to'or'
less'than'1/2'psi'(14”'w.c.'[3.5'kPa]).
WARNING:$Install$a$gas$
pressure$regulator,$in$the$
gas$supply$line,$which$does$
not$exceed$the$maximum$
supply$pressure.
DO$NOT$use$an$industrial$
type$gas$regulator.
18