Combat® UHD[S] 150 - UHD[S] 400 Clearances and Dimension Data
Clearances to Combustibles - Low Profile UHD[S] Range (Models 75 - 125)
Above Heater | Below Heater | To Side of Heater | Access Side Door | To Flue |
|
|
|
|
|
6" | 6" | 6" | 31" Access Clearance | 2" |
|
|
|
|
|
Dimension Data - Standard UHD[S] Range (Models 150 - 400)
Model |
| 150 | 175 | 200 | 225 | 250 | 300 | 350 | 400 | |
|
|
|
|
|
|
|
|
|
| |
'A' Width | [in] | 43 | 43 | 43 | 43 | 43 | 50 | 50 | 50 | |
|
|
|
|
|
|
|
|
|
| |
'B' Height | [in] | 27 | 27 | 35.25 | 35.25 | 35.25 | 43.5 | 43.5 | 43.5 | |
|
|
|
|
|
|
|
|
|
| |
'C' Duct Connectors | [in] | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | |
|
|
|
|
|
|
|
|
|
| |
'D' Support Spacing | [in] | 17.6 | 17.6 | 17.6 | 17.6 | 17.6 | 24.7 | 24.7 | 24.7 | |
|
|
|
|
|
|
|
|
|
| |
'F' Center of Flue | [in] | 9.5 | 9.5 | 17 | 17 | 17 | 13.6 | 13.6 | 13.6 | |
|
|
|
|
|
|
|
|
|
| |
'G' Flue Center to |
| 6 | 6 | 6 | 6 | 6 | 7 | 7 | 7 | |
Air Intake Center | [in] | |||||||||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| |
'H' Position of Flue | [in] | 4.5 | 4.5 | 4.75 | 4.75 | 4.75 | 4.9 | 4.9 | 4.9 | |
|
|
|
|
|
|
|
|
|
| |
'J' Gas Inlet Position | [in] | 5.9 | 5.9 | 5.9 | 5.9 | 5.9 | 8.7 | 8.7 | 8.7 | |
|
|
|
|
|
|
|
|
|
| |
'K' Electrical Supply Position | [in] | 3.4 | 3.4 | 3.4 | 3.4 | 3.4 | 6.2 | 6.2 | 6.2 | |
|
|
|
|
|
|
|
|
|
|
| Top View | Heater must be supported | |
|
| at these points from above | |
|
| or below. | D |
|
|
| |
|
|
| C |
|
|
| 4 x 3/8” Captive Nuts Provided |
CentersSupport | 19.4” |
|
|
End View
C
Rear View |
|
| 25.5” | ||
|
| ||||
|
|
|
|
|
|
| Air Intake |
|
|
| (UHDS only) |
| |
F |
|
|
|
|
| G |
|
| H | Flue |
|
|
|
| |
|
| Gas |
|
| Thermostat | Supply |
|
|
|
| |
| Connection |
|
|
6.5” | Electrical |
| |
| Supply |
| |
| 2.4” |
|
|
| K |
|
|
| J |
| A |
|
|
|
B