RuggedServer™ RS401

4-Port Serial Device Server with Integrated 4-Port Managed Ethernet Switch

Power Supply

￿.Power Consumption: 8W (max)

￿.24VDC: 9-36VDC (max)

￿.48VDC: 36-59VDC (max)

￿.HI Voltage AC/DC: 88-300VDC, 85-264VAC (max)

Critical Alarm Relay

￿.Form-C failsafe contact relay: 1A@30VDC

Physical

￿.Height: 3.5" (8.9cm)

￿.Width: 6.76" (17.2cm)

￿.Depth: 7.42" (18.8cm)

￿.Weight: 4.15lbs (1.9 Kg)

￿.Ingress Protection: IP40 (1mm objects)

￿.Enclosure: 18 AWG galvanized steel enclosure

￿.Mounting: DIN rail or panel mounted

Switch Properties

￿.Switching method: Store & Forward

￿.Switching latency: 5 us (100Mbps)

￿.Switching bandwidth: 1.2Gbps

￿.MAC addresses: 2048

￿.MAC address table size: 16kbytes

￿.Priority Queues: 4

￿.Frame buffer memory: 1-Mbit

￿.VLANs: 16

￿.IGMP multicast groups: 256

Approvals

￿.ISO: Designed and manufactured using a ISO9001: 2000 certified quality program

￿.CE Marking

￿.Emissions: FCC Part 15 (Class A), EN55022 (CISPR22 Class A)

￿.Safety: cCSAus (Compliant with CSA C22.2 No. 60950, UL 60950, EN60950)

￿.Laser Eye Safety (FDA/CDRH): Complies with 21 CFR Chapter1, Subchapter J.

Warranty

￿.5 Years-Applicable to design or manufacturing related product defects.

Network Management

￿.Web-based graphical HTML ￿.SNMP v1, v2c

￿.Telnet, VT100

￿.Command Line Interface (CLI)

Technical Specifications

EMI Immunity and Environmental Compliance

￿.IEC 61000-6-2 Industrial (Generic)

￿.IEC 61800-3 Industrial (Variable Speed Drive Systems) ￿.IEC 61850-3 Electric Utility Substations

￿.IEEE 1613 Electric Utility Substations

￿.NEMA TS 2 Traffic Control Equipment

IEEE Compliance

￿.802.3-10BaseT

￿.802.3u-100BaseTX, 100BaseFX ￿.802.3x-Flow Control ￿.802.3d-MAC Bridges ￿.802.1d-Spanning Tree Protocol ￿.802.1p-Class of Service ￿.802.1q-VLAN Tagging

￿.802.1w-Rapid Spanning Tree Protocol

IETF RFC Compliance

￿.RFC791-IP

￿.RFC792-ICMP

￿.RFC793-TCP

￿.RFC783-TFTP

￿.RFC826-ARP

￿.RFC768-UDP

￿.RFC894-IP over Ethernet ￿.RFC854-Telnet ￿.RFC1519-CIDR ￿.RFC1541-DHCP (client) ￿.RFC1112-IGMP v1 ￿.RFC 1661-PPP ￿.RFC2236-IGMP v2 ￿.RFC2030-SNTP ￿.RFC2068-HTTP

IETF SNMP MIBS

￿.RFC1493-BRIDGE-MIB ￿.RFC1907-SNMPv2-MIB ￿.RFC2012-TCP-MIB ￿.RFC2013-UDP-MIB ￿.RFC2578-SNMPv2-SMI ￿.RFC2579-SNMPv2-TC ￿.RFC2819-RMON-MIB ￿.RFC2863-IF-MIB ￿.draft-ietf-bridge-rstpmib-03-BRIDGE-MIB

￿.draft-ietf-bridge-bridgemib-smiv2-03-RSTP-MIB ￿.IANAifType-MIB

Fiber Optical Specifications

Parameter

 

 

Fiber Port Type

 

 

 

 

 

 

 

 

 

 

 

10BaseFL

 

 

100BaseFX

 

 

 

 

 

 

 

 

Mode

Multimode

Multimode

 

 

Singlemode

 

 

 

 

 

 

 

 

Connectors

ST

MTRJ / ST / SC

 

 

LC / SC

 

Typical Dist. (km)

2

2

20

 

50

90

Optical Wavelength (nm)

820

1310

 

1310

 

Cable Size Core/Cladding (um)

50 or 62.5/125

50 or 62.5/125

 

 

8 or 9/125

 

 

 

 

 

 

 

 

Tx Power (dBm)

-34.4

-15.7

-15.5

 

-2.5

2.5

 

 

 

 

 

 

 

Rx Sensitivity (dBm)

-8.2

-33.5

-32

 

-37

-39

 

 

 

 

 

 

 

Typical Budget

22

17

16.5

 

34.5

41.5

 

Longer segment lengths dependent on fiber specifications. Consult factory for further details.

 

 

 

 

 

 

 

 

www.RuggedCom.com

RuggedSwitchTM RS401

6

 

 

 

 

 

Page 6
Image 6
RuggedCom RS401 warranty Technical Specifications, Ietf Snmp Mibs