3.6 Type Test Specifications
  | Electrical Safety | Levels | 
  | 
  | Comments | |
  | Dielectric Withstand  | 2 kV rms for 1 minute  | 
  | 
  | ANSI/IEEE C37.90 (1989)  | |
  | 
  | 
  | 
  | 
  | 
  | IEC   | 
  | High Voltage Impulse  | 5 kV peak  | 
  | 
  | IEC   | |
  | Insulation Resistance  | 500 VDC for 1 minute  | 
  | 
  | IEC   | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Electrical Environment | Levels  | 
  | 
  | Comments  | |
  | High Frequency Disturbance  | 2.5 kV @ 1MHz for 2s  | 
  | 
  | ANSI/IEEE C37.90.1  | |
  | (Oscillatory)  | 
  | 
  | 
  | 
  | IEC   | 
  | IEC Surge  | 4 kV / 2 kV  | 
  | 
  | IEC   | |
  | 
  | 
  | 
  | 
  | 
  | (Level 4)  | 
  | IEC Fast Transient  | 2 kV / 1 kV  | 
  | 
  | IEC   | |
  | 
  | 
  | 
  | 
  | 
  | (Level 4)  | 
  | ANSI/IEEE Fast Transient  | 4 kV  | 
  | 
  | ANSI/IEEE C37.90.1  | |
  | IEC Radiated RFI Immunity  | 10 V/m  | 
  | 
  | IEC   | |
  | ANSI/IEEE Radiated RFI  | 35 V/m  | 
  | 
  | ANSI/IEEE C37.90.2  | |
  | Immunity  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | |
  | ESD  | 15 kV (air discharge)  | 
  | 
  | IEC   | |
  | (Electrostatic Discharge)  | 8 kV (contact)  | 
  | 
  | (Level 4)  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Atmospheric Environment  | Levels  | 
  | 
  | 
  | Comments  | 
  | Temperature (Dry Cold)  | 
  | 
  | 
  | IEC   | |
  | 
  | 
  | 
  | Test Ad: 16 hrs @  | ||
  | Temperature (Dry Heat)  | 85°C  | 
  | 
  | 
  | IEC   | 
  | 
  | 
  | 
  | Test Bd: 16 hrs @ 85°C | ||
  | Humidity  | 95% | 
  | 
  | 
  | IEC   | 
  | 
  | 
  | Test Db: 6 cycles, 55°C, 95%  | |||
  | 
  | 
  | 
  | 
  | 
  | Humidity  | 
  | 14  | 
 2008 RuggedCom Inc. All rights reserved | Rev101  |