RuggedCom EMI and Environmental Type Tests, RuggedWirelessTM RS900W, RuggedWireless RS900W

Models: RS900W

1 9
Download 9 pages 27.06 Kb
Page 6
Image 6
EMI and Environmental Type Tests

RuggedWirelessTM RS900W

Wireless Ethernet with Integrated 8-Port Managed Switch

EMI and Environmental Type Tests

NEMA TS-2 Requirements

 

Test

 

 

 

 

 

Description

 

 

 

Levels

 

 

 

Performance Criteria*

 

TS-2 1998, Section 2, para 2.2.7.3

 

Temperature: Low Temperature/Low

 

89.0 VAC @ -34°C

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TS-2 1998, Section 2, para 2.2.7.4

 

Temperature: Low Temperature/High

 

135.0VAC @ -34°C

EUT Continued to function properly during

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and following all temperature and humidity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature: High Temperature/High

 

 

 

 

 

 

TS-2 1998, Section 2, para 2.2.7.5

 

 

135.0VAC @ + 75°C

 

 

testing

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TS-2 1998, Section 2, para 2.2.7.6

 

Temperature: High Temperature/Low

 

89.0VAC @ + 75°C

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TS-2 1998, Section 2 para. 2.2.8.4

 

Vibration Endurance Test

 

0.5g @ 30Hz for 1hr on all three planes

EUT functioned properly following test pro-

 

 

 

cedure. No physical damage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TS-2 1998, Section 2, para 2.1.10

 

 

Mechanical Shock

 

+/-10g half sine wave for 11msec on all

EUT functioned properly following test pro-

 

 

 

 

 

three planes

 

cedure. No physical damage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Transients: High Repetition Noise

One +/-300VDC pulse every other cycle

EUT functioned properly during and follow-

 

TS-2 1992, Section 2, para. 2.1.6.1

 

once every 3 seconds across 360 ° of line

 

 

 

 

 

 

(AC Terminals)

 

 

cycle (2500W peak)

ing test procedure. No damage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TS-2 1998, Section 2 para. 2.1.6.2

 

Electrical Transients: Low-Repetition High

One +/-600VDC pulse every second, ran-

EUT functioned properly during and follow-

 

 

Energy (AC Terminals

 

domly distributed across 360 ° of line

ing test procedure. No damage

 

 

 

 

 

 

 

cycle. Ten pulses total.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TS-2 1998, Section 2, para 2.1.7

 

Electrical Transients: I/O Terminals

 

One +/-300VDC pulse every second, mini-

EUT functioned properly during and follow-

 

 

 

 

mum 5 pulses per port

ing test procedure. No damage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TS-2 1992, Section 2, para. 2.1.8

 

Electrical Transients: Nondestruct

 

One +/-1000VDC pulse every two seconds,

EUT functioned properly following test pro-

 

 

Transient Immunity (AC Terminals)

 

 

3 per each polarity.

 

cedure. No damage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-6-2 EMC Generic Standard: Immunity for Industrial Environments

 

 

 

 

Test

 

 

 

Description

 

 

Levels

 

RuggedCom Test Level

Performance Criteria*

 

IEC 61000-4-2

 

 

ESD

 

Enclosure Contact

 

 

+/- 4kV

 

+/- 8kV

B

 

 

 

 

Enclosure Air

 

 

+/- 8kV

 

+/- 15kV

B

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-3

 

Radiated RFI

 

Enclosure ports

 

10 V/m, 80 to 1000Mhz

 

20V/m

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal ports

 

 

+/- 1kV @ 5kHz

 

+/- 4kV @ 2.5kHz

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-4

Burst (Fast Transient)

 

D.C Power ports

 

 

+/- 2kV @ 5kHz

 

+/- 4kV

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

 

 

+/- 2kV @ 5kHz

 

+/- 4kV

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal ports

 

 

+/- 1kV line-to-earth

 

+/- 2kV line-to-earth, +/- 2kV

B

 

 

 

 

 

 

 

 

 

 

line-to-line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-5

 

 

Surge

 

D.C Power ports

 

+/- 0.5kV line-to-earth/line

+/- 4kV line-to-earth, +/- 2kV

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

line-to-line

 

 

 

 

 

 

 

 

A.C. Power ports

 

+/- 2kV line-to-earth, +/- 1kV

+/- 4kV line-to-earth, +/- 2kV

B

 

 

 

 

 

 

 

 

 

line-to-line

 

line-to-line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal ports

 

 

10V @ 0, 5-80 MHz

 

10V @ 0, 5-80 MHz

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D.C Power ports

 

 

10V @ 0, 5-80 MHz

 

10V @ 0, 5-80 MHz

A

 

IEC 61000-4-6

Induced (Conducted) RFI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

 

 

10V @ 0, 5-80 MHz

 

10V @ 0, 5-80 MHz

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Earth ground ports

 

 

10V @ 0, 5-80 MHz

 

10V @ 0, 5-80 MHz

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-8

 

Magnetic Field

 

Enclosure ports

 

 

30 A/m @ 50, 60 Hz

 

40 A/m continuous, 1000

A

 

 

 

 

 

 

A/m for 1s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30% reduction for 0.5

 

30% for 1 period

B

 

 

 

 

 

 

 

 

 

 

 

period

 

 

IEC 61000-4-11

 

Voltage Dips

 

A.C. Power ports

 

 

 

 

 

 

 

 

 

 

 

>95% reduction for 250

 

100% for 5 periods, 100%

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

periods

 

for 50 periods

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal ports

 

 

2kVac

 

2kVac

N/A

 

 

 

 

 

 

 

 

(Fail-Safe Relay output)

 

(Fail-Safe Relay output)

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 60255-5

Dielectric Strength

 

D.C. Power ports

 

 

2kVac

 

2kVac

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

 

 

2kVac

 

2kVac

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal ports

 

 

5kV

 

5kV

N/A

 

 

 

 

 

 

 

 

(Fail-Safe Relay output)

 

(Fail-Safe Relay output)

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 60255-5

 

H.V. Impulse

 

D.C. Power ports

 

 

5kV

 

5kV

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

 

 

5kV

 

5kV

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Environmental Type Tests

 

 

 

 

 

 

Test

 

 

 

 

 

Description

 

 

 

 

 

Test Levels

 

 

Severity Levels

 

IEC 60068-2-1

 

 

 

Cold Temperature

 

Test Ad

 

 

-40°C, 16 Hours

 

 

N/A

 

IEC 60068-2-2

 

 

 

Dry Heat

 

Test Bd

 

 

+85°C, 16 Hours

 

 

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 60068-2-30

 

Humidity (Damp Heat, Cyclic)

 

Test Db

 

95% (non-condensing),

 

N/A

 

 

 

 

 

55°C , 6 cycles

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 60255-21-1

 

 

 

Vibration

 

Tests Fc

 

2g @ (10 - 150) Hz

 

Class 2 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 60255-21-2

 

 

 

Shock

 

 

 

Tests Ea

 

 

30g @ 11mS

 

 

Class 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes: 1. Class 2 refers to "Measuring relays and protection equipment for which a very high security margin is required or where the vibration levels are very high, ( e.g. shipboard application and for severe transportation conditions")

www.RuggedCom.com