Sanyo 12RS11, 12RLS11 specifications 1B INSTALLATION

Models: 12RLS11 12RS11

1 3
Download 3 pages 17.85 Kb
Page 2
Image 2

outdoor air temperature (selected systems), automatic indoor fan speed determined by system microprocessor, washable anti-mold poly filters, indoor mounted operation selector & lamp showing operation, standby & timer modes, with start up test mode & manual on/off switch.

Low Ambient Systems shall be capable of operating in tne cooling mode down to zero (0) degrees F. outdoor temperature.

1B) INSTALLATION

System(s) shall be installed according to manufacturer’s instructions & recommendations, as well as, all governing local & national codes. System(s), as well as the infrared remote controller, shall be mounted & placed as shown on plans within all minimum clearances as specified by manufacturer’s instructions, & secured to provide for safe operation. Refrigerant tubing size shall not vary from manufacturer’s specifications, and shall be properly secured & insulated. Installer shall insulate both liquid & suction lines individually. Electrical wiring shall be sized & installed according to manufacturer’s instructions & in conformance with the National Electric Code (N.E.C.). Outdoor condensers shall be mounted & secured to accommodate for extreme weather conditions. Distance between indoor & outdoor unit(s) shall not exceed manufacturer’s specifications.

2)OUTDOOR CONDENSING SECTIONSANYO MODELS C1211, CL1211

Outdoor condensing section(s) shall be factory assembled, wired, piped & pre-charged with a start up amount of R-22 refrigerant. Unit(s) shall be constructed of G90 galvannealed steel with corrosion inhibiting, acrylic, baked-on enamel finish. Unit(s) shall be furnished with a high efficiency, Sanyo rotary compressor with internal overload protection, securely mounted with vibration isolators to reduce noise & vibration. Condenser coil heat exchanger shall be constructed of nonferrous, rifled copper tubing with enhanced aluminum slit fins mechanically bonded to the copper. A suction line accumulator, a coil temperature sensor & cap tube metering device shall be factory installed. Fan motor(s) shall be direct drive with internal overload protection, permanent lubrication, with propeller type fan(s), mounted for horizontal air discharge. Brass valves with refrigeration flare connections & flare nuts, & service ports shall be factory mounted, externally for easy access. The unit(s) shall be test started by the manufacturer at their factory prior to shipment for installation.

Low Ambient outdoor section(s) shall contain a printed circuit board, factory mounted & wired, to assist in control of low ambient operation. Unit(s) shall be able to operate in the A/C mode down to zero (0) degrees Fahrenheit outdoor temperature. A factory installed 20 watt crankcase heater shall provide additional compressor protection.

3) INDOOR EVAPORATOR SECTION – SANYO MODELS – RS1211

Indoor section(s) shall be recessed ceiling mount type, with single direction airflow, factory assembled & wired. Ceiling mounting diagram shall be included with each system. Unit(s) shall contain an evaporator heat exchanger constructed of nonferrous, rifled copper tubing with enhanced aluminum slit fins, mechanically bonded to the copper. A single centrifugal blower wheel, statically & dynamically balanced shall be attached to a single direct drive, PSC fan motor, with overload protection, permanent lubrication & multi-speed capability. Unit(s) shall contain a Printed Circuit Board (PCB) with a control circuit fuse & microprocessor, factory mounted &