Sanyo dimensions Split System Submittal Data, System 18KS72 Indoor/Outdoor KS1872/C1872, Power

Models: 18KS72

1 2
Download 2 pages 55.84 Kb
Page 1
Image 1
Split System Submittal Data

Print Form

Split System Submittal Data

System: 18KS72 Indoor/Outdoor: KS1872/C1872

Wall Mounted Air Conditioner

Job Name:

Location:

Engineer:

Submitted to:

Submitted by:

Reference:

 

General Data (at 230V)

Power
V/PH/Hz
230/208/1/60

Circuit Ampacity

(A)

20

Fuse Size, Max.

(A)

20

Compressor

 

DC Rotary Inverter

No. used

 

1

R.L. Amps - L.R.

(A)

7 - 17.5

Crankcase Heater

(W)

N/A

Outdoor Unit

 

 

Fan type

 

Propeller

Dia. (in.) - No. Speeds

 

16-17/32 - 1

Type Drive - No. Speeds

 

DC Motor

No. Poles

(RPM)

8 - 820

No. Motors

(W)

50 - 1

CFM

(High)

524

F.L. Amps

(A)

0.5

Coil Type

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

Corrugated Plate - Inner Riffed

Rows - F.P.I.

 

2 - 21.2

Face Area

(sq.ft.)

5.49

Tube Size

(in.)

9/32”

Indoor Unit

 

 

Fan type

 

Cross Flow

Dia. & Length (in.) - No. Speeds

3-11/16 33-9/32 - 1

No. Speeds

 

3 & Auto

No. Poles

(RPM, High)

8 - 1250

No. Motors

(W)

30 - 1

CFM

(HI/Med/Lo)

523/470/417

Indoor Sound Rating

(Hi) (dB-A)

42

F.L. Amps

(A)

0.3

Coil Type

Aluminum Plate Fin & Copper Tube

Fin Type - Pipe Type

 

Slit Plate - Inner Riffed

Rows - F.P.I.

 

2 - 19.5

Face Area

(sq.ft.)

3.07

Tube Size

(in.)

9/32”

Drain Connection Size

(in.)

23/32”

Approval:

Date:

Construction:

Unit #:

Drawing #:

Refrigerant

 

 

 

R410A

Lbs. - R410a (outdoor unit)

 

 

2.87

Control

 

 

Electric Expansion Valve

Connection

 

 

 

Flare

Line Length, Max

 

 

 

100

Lift Difference, Max

 

 

 

50

Line Size

(in. O.D. Discharge)

1/4”

Line Size

(in. O.D. Suction)

1/2”

Dimensions

(in.)

 

H x W x D

Indoor Unit

(Uncrated)

11-23/32 x 41-15/16 x 8-19/32

Outdoor Unit

(Crated)

 

11-3/8 x 44-7/8 x 14-29/32

(Uncrated)

26-3/8 x 34-21/32 x 11-7/32

 

(Crated)

29-1/8 x 39-27/32 x 14-31/32

Weight

Indoor

 

Outdoor

Net

(lbs.)

26.5

 

90.4

Shipping

(lbs.)

33.1

 

99.2

Shipping Volume

 

Indoor

 

Outdoor

(cu.ft.)

4.23

 

9.88

Performance Data @ ARI Standard Conditions (230V)

 

Cooling

 

 

 

 

Total Capacity

 

(BTU/H)

17,500 (4,000-17,500)

Sensible Capacity

 

(BTU/H)

 

13,100

Latent Capacity

 

(BTU/H)

 

4,400

SEER

 

 

 

20

Dehumidification

 

(Pints/H)

 

4.89

Amps

 

(A)

 

7/7.7

Power Inputs

(W)

1,500/1,500 (250-1,500)

Outdoor Sound Rating

(dB-A)

 

51

Page 1