1B) System Features will include: Sanyo high efficiency, rotary compressor, with suction line accumulator, cap tube refrigerant control, light duty condensate pump, indoor coil freeze protection,
Low Ambient System(s) shall be capable of operating in the cooling mode down to zero (0) degrees F. outdoor temperature.
1C) INSTALLATION
System(s) shall be installed according to manufacturer’s instructions & recommendations, as well as, all governing local & national codes. System(s), as well as the infrared remote controller, shall be mounted & placed as shown on plans within all minimum clearances as specified by manufacturer’s instructions, & secured to provide for safe operation. Refrigerant tubing size shall not vary from manufacturer’s specifications, and shall be properly secured & insulated. Installer shall insulate both liquid & suction lines individually. Electrical wiring shall be sized & installed according to manufacturer’s instructions & in conformance with the National Electric Code (NEC)
&local codes. Outdoor condensers shall be mounted & secured to accommodate for extreme weather conditions. Distance between indoor & outdoor unit(s) shall not exceed manufacturer’s specifications.
2)OUTDOOR CONDENSING SECTION – SANYO MODELS – C1852, CL1852
Outdoor condensing section(s) shall be factory assembled, wired, piped &
Low Ambient outdoor section(s) shall contain a printed circuit board, factory mounted & wired, to assist in control of low ambient operation. Unit(s) shall be able to operate in the A/C mode down to zero (0) degrees Fahrenheit outdoor temperature. A factory installed 20 watt crankcase heater shall provide additional compressor protection.
3) INDOOR EVAPORATOR SECTION – SANYO MODELS – XS1852
Indoor section(s) shall be recessed ceiling mount type, with four (4) way airflow, factory assembled & wired. Ceiling mounting diagram shall be included with each system. Unit(s) shall contain an evaporator heat exchanger constructed of nonferrous, rifled copper tubing with enhanced aluminum slit fins, mechanically bonded to the copper. A single turbo type blower wheel, statically & dynamically balanced shall be attached to a single direct drive, PSC fan motor,