Sanyo 24THS32 dimensions Submittal Sheet, System, THS2432/CH2432, Indoor/Outdoor, Feature, Option

Models: 24THS32

1 2
Download 2 pages 38.42 Kb
Page 1
Image 1
SUBMITTAL SHEET

SUBMITTAL SHEET

SYSTEM

 

INDOOR/OUTDOOR

24THS32

 

THS2432/CH2432

CEILING SUSPENDED HEAT PUMP

 

 

 

GENERAL DATA

(AT 230V)

POWER

V/PH/HZ

 

 

230/208/1/60

Circuit Ampacity, Min. (A)

30

 

Fuse size, Max

(A)

30

 

COMPRESSOR

 

 

Rotary-Hermetic

No. used

 

 

 

1

 

 

R.L. Amps - L.R. Amps (A)

9.4 - 66.0

Crankcase Heater

 

 

30W

 

OUTDOOR FAN - TYPE

Propeller

Dia. (in.) - No. used

 

 

18-3/32- 1

Type Drive - No. speeds

Direct ñ 2 (AUTO)

No. Poles - RPM (High)

 

6 - 879

 

No. Motors ñ HP

 

 

1 - 1/7

 

CFM (High)

 

 

1,840

 

F.L. Amps. (A)

 

 

0.9

 

OUTDOOR COIL ñ TYPE

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

 

 

Slit Plate - Inner Riffled

Rows - F.P.I.

 

 

2- 14.1

 

Face Area

(sq.ft.)

 

 

6.78

 

Tube Size

(in.)

 

 

3/8

 

INDOOR FAN ñ TYPE

 

 

Centrifugal

Dia. & Length (in.) - No. used

5-1/8 & 4

No. speeds

 

 

 

3 & Auto

No. Poles -RPM (High)

 

4-1,187

No. Motors - HP

 

 

1 - 1/24

CFM (HI/MED/LOW)

 

 

540/490/425

F.L. Amps (A)

 

 

0.4

 

INDOOR COIL - TYPE

 

 

Aluminum Fin & Copper Pipe

Fin Type - Pipe type

 

 

Slit Plate - Inner Riffled

Rows - F.P.I.

 

 

3 - 14.9

Face Area

(sq. ft.)

 

 

1.81

 

Tube Size

(in.)

 

 

3/8

 

Drain Connection Size (in.)

1-1/4

 

REFRIGERANT

 

 

R22

 

Lbs. - R22

(O.D. Unit)

 

 

6.17

 

Control

 

 

 

 

Capillary Tube

Connection

 

 

 

Electronic Refrigerant Control Valve

Line Length, Max (ft.)

 

 

165

 

Lift difference, Max (ft.)

 

100

 

Line Size - in. O.D. Discharge

1/4

 

Line Size - in. O.D. Suction

3/4

 

DIMENSIONS (in.)

 

H x

W

x

D

Indoor Unit

-Uncrated

 

7- 15/32

x 51- 6/32 x 26-3/8

 

 

-Crated 9- 14/32

x 54- 19/32 x 29-31/32

Outdoor Unit-Uncrated

 

28-15/16

x 37

x 13-3/8

 

 

-Crated

32-17/32

x 40

x 16-12/32

WEIGHT

 

 

INDOOR

OUTDOOR

Net

(lbs.)

 

60.0

 

 

157.0

Shipping(lbs.)

 

77.0

 

 

170.0

Shipping Volume (cu.ft.)

8.9

 

 

12.3

AIRCONDITIONING PRODUCTS

SS24THS32-1

PERFORMANCE DATA @ ARI STANDARD CONDITIONS (230/208V)

COOLING

 

 

 

Total Capacity

(BTU/H)

22,400/21,600

Sensible Capacity (BTU/H)

13,640/12,970

Latent Capacity

(BTU/H)

8,760/8,630

SEER

 

 

10.0/10.0

Dehumidification

(Pints/H)

6.3/6.2

Amps (A)

 

 

10.7/11.3

Power Inputs (W)

 

 

2,290/2,250

HEATING

 

 

 

Total Capacity

(BTU/H)

25,400/25,000

HSPF

 

 

7.0/7.0

Amps (A)

 

 

11.7/12.9

Power Inputs (W)

 

 

2,350/2,280

Back-up Strip Heater (KW)

1.80/1.47

Outdoor Sound Rating(bels)

7.6

FEATURE

 

 

 

Controls

 

 

Microprocessor

Remote Controller

 

 

LCD Wireless type

Temperature Control

 

IC Thermostat

Timer

 

 

ON/OFF, 24 hours

Night Setback

 

 

Built-In

Air Louver (Horizontal)

Manual

(Vertical)

 

Automatic

Power Failure Automatic Restart

Built-In

Self Diagnosis

 

 

N/A

OPTION

 

 

 

Refrigerant Line Set

 

AP2710BH (30 ft)

 

 

 

AP2715BH (50 ft)

Low Ambient Control

 

Built-In

Fresh Air Intake

 

 

N/A

Central Remote ON-OFF Control

Available

Airduct Extension

 

 

N/A

Indoor Frame Extension

N/A

Condensate Drain Pump

Available

Non-Removable Remo-con Bracket

RCS5PS4B

OPERATING RANGE

 

 

Cooling

 

Indoor Air

Outdoor Air

 

 

Intake Temp.

Intake Temp.

Maximum

95F DB/71F WB

115F DB

Minimum

67F DB/57F WB

23F DB

Heating Maximum

80F DB/67F WB

75F DB/67F WB

Minimum

-F DB/ - F WB

17F DB/15F WB

CERTIFICATION

24THS32

Page 1
Image 1
Sanyo 24THS32 dimensions Submittal Sheet, System, THS2432/CH2432, Indoor/Outdoor, Airconditioning Products, Feature