Sanyo 36KHS72R dimensions Split System Submittal Data, Wall Mounted Heat Pump, Power, V/PH/Hz

Models: 36KHS72R

1 2
Download 2 pages 48 Kb
Page 1
Image 1
Split System Submittal Data

Print Form

Split System Submittal Data

System: 36KHS72R Indoor/Outdoor: KHS3672R/CH3672R

Wall Mounted Heat Pump

Job Name:

Location:

Engineer:

Submitted to:

Submitted by:

Reference:

 

General Data (at 230V)

Power
V/PH/Hz
230/208/1/60

Circuit Ampacity

(A)

15-35 Indoor-Outdoor

Fuse Size, Max.

(A)

15-35 Indoor-Outdoor

Compressor

 

DC Rotary Inverter

No. used

 

1

R.L. Amps - L.R.

(A)

16.4-17.5

Crankcase Heater

(W)

-

Outdoor Unit

 

 

Fan type

 

Propeller

Dia. (in.) - No. Speeds

 

18-7/64-1

Type Drive - No. Speeds

 

DC Motor

No. Poles

(RPM)

8 - 830

No. Motors

(W)

1 - 90

CFM

(High)

1942

F.L. Amps

(A)

17.3

Coil Type

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

 

Slit Plate - Inner Riffeled

Rows - F.P.I.

 

2 - 14.1

Face Area

(sq.ft.)

7.26

Tube Size

(in.)

3/8”

Indoor Unit

 

 

Fan type

 

Cross Flow

Dia. & Length (in.) - No. Speeds

4-13/18 L46 - 1

No. Speeds

 

3 & Auto

No. Poles

(RPM, High)

4 - 1273

No. Motors

(W)

1 - 50

CFM

(HI/Med/Lo)

830/710/590

Indoor Sound Rating

(Hi) (dB-A)

48

F.L. Amps

(A)

0.5

Coil Type

Aluminum Plate Fin & Copper Tube

Fin Type - Pipe Type

 

Slit Plate - Inner Riffeled

Rows - F.P.I.

 

3 - 12.7

Face Area

(sq.ft.)

3.23

Tube Size

(in.)

3/8”

Drain Connection Size

(in.)

1-1/4”

Approval:

Date:

Construction:

Unit #:

Drawing #:

Refrigerant

 

 

 

 

R410A

Lbs. - R410a (outdoor unit)

 

 

 

 

6.17

Control

 

 

Electric Expansion Valve

Connection

 

 

 

 

Flare

Line Length, Max (ft.)

 

 

 

 

165

Lift Difference, Max (ft.)

50 (outdoor lower), 100 (outdoor higher)

Line Size

 

(in. O.D. Discharge)

3/8”

Line Size

 

(in. O.D. Suction)

5/8”

Dimensions

 

(in.)

 

 

H x W x D

Indoor Unit

(Uncrated)

14-9/16 x 59-1/16 x 9-7/16

Outdoor Unit

(Crated)

18-7/16 x 62-9/16 x 12-9/16

 

(Uncrated)

30-23/32 x 37 x 13-3/8

(Crated)

34-31/32 x 39-31/32 x 16-3/32

Weight

 

Indoor

 

 

Outdoor

Net

(lbs.)

72.8

 

 

143

Shipping

(lbs.)

90.4

 

 

161

Shipping Volume

 

Indoor

 

 

Outdoor

(cu.ft.)

8.4

 

 

13.0

Performance Data @ ARI Standard Conditions (230/208V)

Cooling

 

 

 

 

 

Total Capacity

 

(BTU/H)

31,400 (9,500-31,400)

Sensible Capacity

 

(BTU/H)

 

18,760

Latent Capacity

 

(BTU/H)

 

12,640

SEER

 

 

 

 

15.9

Dehumidification

 

(Pints/H)

 

10.0

Amps

 

(A)

 

 

17.9/19.8

Power Inputs

 

(W)

 

 

3,750/3,750

Outdoor Sound Rating

 

(dB-A)

 

 

52

Heating

 

 

 

 

 

Total Capacity

 

(BTU/H)

36,400 (8,000-36,400)

HSPF

 

 

 

 

9