Sanyo dimensions Split System Submittal Data, System 36UHW72R, Concealed Duct Heat Pump, Power

Models: 36UHW72R

1 2
Download 2 pages 33.68 Kb
Page 1
Image 1
Split System Submittal Data

Print Form

Split System Submittal Data

System: 36UHW72R

Indoor/Outdoor: UHW3672R/CH3672R

Concealed Duct Heat Pump

 

Job Name:

Location:

Engineer:

Submitted to:

Submitted by:

Reference:

 

General Data (at 230V)

Power

V/PH/Hz

230/208/1/60

Circuit Ampacity

(A)

15-35 Indoor-Outdoor

Fuse Size, Max.

(A)

15-35 Indoor-Outdoor

Compressor

 

DC Rotary

No. used

 

1

R.L. Amps - L.R.

(A)

16.4

Outdoor Unit

 

 

Fan type

 

Propeller

Dia. (in.) - No. Speeds

 

18-7/64-1

Type Drive - No. Speeds

 

Direct - Inverter

No. Poles

(RPM)

8-830

No. Motors

(W)

1-90

CFM

(High)

1942

F.L. Amps

(A)

17.3

Coil Type

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

 

Slit Plate - Inner Rifed

Rows - F.P.I.

 

2-14.1

Face Area

(sq.ft.)

7.26

Tube Size

(in.)

3/8”

Indoor Unit

 

 

Fan type

 

Centrifugal

Dia. & Length (in.) - No. Speeds

5-29/32-3

No. Speeds

 

3 & Auto

No. Poles

(RPM, High)

4-940

No. Motors

(W)

1-100

CFM

(HI/Med/Lo)

1060/920/750

Indoor Sound Rating

(Hi) (dB-A)

38

F.L. Amps

(A)

1.0

Coil Type

Aluminum Plate Fin & Copper Tube

Fin Type - Pipe Type

 

Slit Plate - Inner Rifed

Rows - F.P.I.

 

3-12.7

Face Area

(sq.ft.)

3.32

Tube Size

(in.)

3/8”

Drain Connection Size

Max. head 2-33/64in. above drain connection (1-17/64)

Approval:

Date:

Construction:

Unit #:

Drawing #:

Refrigerant

 

 

 

R410A

Lbs. - R410a (outdoor unit)

 

 

6.17

Control

 

Electric Expansion Valve

Connection

 

 

 

Flare

Line Length, Max (ft.)

 

 

 

165

Lift Difference, Max (ft.)

50 (Outdoor lower), 100 (Outdoor higher)

Line Size

(in. O.D. Discharge)

3/8”

Line Size

 

(in. O.D. Suction)

5/8”

Dimensions

(in.)

 

H x W x D

Indoor Unit

(Uncrated)

12-7/32 x 58-9/32 x 24-13/16

(Crated)

14-3/32 x 65-25/32 x 30-13/16

Outdoor Unit

(Uncrated)

 

30-23/32 x 37 x 13-3/8

 

(Crated)

34-31/32 x 39-31/32 x 16-3/32

Weight

 

Indoor

 

Outdoor

Net

(lbs.)

104

 

143

Shipping

(lbs.)

115

 

161

Shipping Volume

 

Indoor

 

Outdoor

(cu.ft.)

16.5

 

13.0

Performance Data @ ARI Standard Conditions (230/208V)

Cooling

 

 

 

 

Total Capacity

 

(BTU/H)

31,200 (9,500-31,200)

Sensible Capacity

 

(BTU/H)

 

19,570

Latent Capacity

 

(BTU/H)

 

11,630

SEER

 

 

 

14.9

Dehumidification

 

(Pints/H)

 

10.0

Amps

 

(A)

 

18.6/20.6

Power Inputs

 

(W)

 

3,920/3,920

Outdoor Sound Rating

 

(dB-A)

 

52

Heating

 

 

 

 

Total Capacity

 

(BTU/H)

36,200 (8,000-36,200)

HSPF

 

 

 

8.7

Page 1
Image 1
Sanyo dimensions Split System Submittal Data, System 36UHW72R, Concealed Duct Heat Pump, Submitted by Reference, Power