Sanyo 26TW72R dimensions Split System Submittal Data, Ceiling Suspended Air Conditioner, Power

Models: 26TW72R THW2672R

1 2
Download 2 pages 62.52 Kb
Page 1
Image 1
Split System Submittal Data

Print Form

Split System Submittal Data

System: 26TW72R Indoor/Outdoor: THW2672R/C2672R

Ceiling Suspended Air Conditioner

Job Name:

Location:

Engineer:

Submitted to:

Submitted by:

Reference:

 

General Data (at 230V)

Power
V/PH/Hz
230/208/1/60

Circuit Ampacity

(A)

15-30 Indoor-Outdoor

Fuse Size, Max.

(A)

15-30 Indoor-Outdoor

Compressor

 

DC Rotary Inverter

No. used

 

1

R.L. Amps - L.R.

(A)

12.9-17.5

Crankcase Heater

(W)

-

Outdoor Unit

 

 

Fan type

 

Propeller

Dia. (in.) - No. Speeds

 

18-7/64-1

Type Drive - No. Speeds

 

Direct Inverter

No. Poles

(RPM)

8 - 800

No. Motors

(W)

1-90

CFM

(High)

1765

F.L. Amps

(A)

13.8

Coil Type

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

 

Slit Plate - Inner Rifed

Rows - F.P.I.

 

1-15.9

Face Area

(sq.ft.)

7.25

Tube Size

(in.)

3/8”

Indoor Unit

 

 

Fan type

 

Centrifugal

Dia. & Length (in.) - No. Speeds

5-1/8 - 4

No. Speeds

 

3 & Auto

No. Poles

(RPM, High)

4-1179

No. Motors

(W)

1-31

CFM

(HI/Med/Lo)

550/490/460

Indoor Sound Rating

(Hi) (dB-A)

39

F.L. Amps

(A)

0.5

Coil Type

Aluminum Fin & Copper Tube

Fin Type - Pipe Type

 

Slit Plate - Inner Rifed

Rows - F.P.I.

 

3-14.9

Face Area

(sq.ft.)

1.81

Tube Size

(in.)

9/32”

Drain Connection Size

(in.)

(1-1/4)

Approval:

Date:

Construction:

Unit #:

Drawing #:

Refrigerant

 

 

 

R410A

Lbs. - R410a (outdoor unit)

 

 

 

4.19

Control

 

 

Electric Expansion Valve

Connection

 

 

 

Flare

Line Length, Max

 

 

 

165

Lift Difference, Max

50 (Outdoor lower), 100 (Outdoor higher)

Line Size

 

(in. O.D. Discharge)

3/8”

Line Size

 

(in. O.D. Suction)

5/8”

Dimensions

(in.)

 

H x W x D

Indoor Unit

(Uncrated)

7-17/32 x 51-3/16 x 26-3/8

(Crated)

9-7/16 x 54-19/32 x 31-1/16

Outdoor Unit

(Uncrated)

30-23/32 x 37 x 13-3/8

(Crated)

34-31/32 x 39-31/32 x 16-3/32

Weight

 

Indoor

 

Outdoor

Net

(lbs.)

57

 

128

Shipping

(lbs.)

68

 

148

Shipping Volume

 

Indoor

 

Outdoor

(cu.ft.)

8.9

 

13

Performance Data @ ARI Standard Conditions (230/208V)

Cooling

 

 

 

 

Total Capacity

 

(BTU/H)

24,000 (9,500-24,400)

Sensible Capacity

 

(BTU/H)

14,330

Latent Capacity

 

(BTU/H)

10,070

SEER

 

 

 

14.5

Dehumidification

 

(Pints/H)

7.7

Amps

 

(A)

 

15.6/17.3

Power Inputs

 

 

(W)

2,880/2,880

Outdoor Sound Rating

 

(dB-A)

 

49

Page 1
Image 1
Sanyo dimensions Split System Submittal Data, System 26TW72R Indoor/Outdoor THW2672R/C2672R, Submitted by Reference