Split System Submittal Data
System: 36XW72R Indoor/Outdoor: XHW3672R/C3672R
Grille:
Ceiling Recessed Air Conditioner
Print Form
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
| General Data (at 230V) | |
Power | V/PH/Hz | 230/208/1/60 |
Circuit Ampacity | (A) | |
Fuse Size, Max. | (A) | |
Compressor |
| DC Motor |
No. used |
| 1 |
R.L. Amps - L.R. | (A) | |
Outdoor Unit |
|
|
Fan type |
| Propeller |
Dia. (in.) - No. Speeds |
| |
Type Drive - No. Speeds |
| Direct Inverter |
No. Poles | (RPM) | 8 - 830 |
No. Motors | (W) | 1 - 90 |
CFM | (High) | 1942 |
F.L. Amps | (A) | 17.3 |
Coil Type | Aluminum Fin & Copper Pipe | |
Fin Type - Pipe Type |
| Slit Plate - Inner Rifed |
Rows - F.P.I. |
| 2 - 14.1 |
Face Area | (sq.ft.) | 7.26 |
Tube Size | (in.) | 3/8” |
Indoor Unit |
|
|
Fan type |
| Turbo |
Dia. & Length (in.) - No. Speeds | ||
No. Speeds |
| 3 & Auto |
No. Poles | (RPM, High) | |
No. Motors | (W) | 1 - 60 |
CFM | (HI/Med/Lo) | 1050/840/720 |
Indoor Sound Rating | (Hi) | 44 |
F.L. Amps | (A) | 0.9 |
Coil Type | Aluminum Plate Fin & Copper Tube | |
Fin Type - Pipe Type |
| Slit Plate - Inner Rifed |
Rows - F.P.I. |
| |
Face Area | (sq.ft.) | 8.2 |
Tube Size | (in.) | 9/32” |
Drain Connection Size | (in.) |
Approval:
Date:
Construction:
Unit #:
Drawing #:
Refrigerant |
|
|
|
|
| R410A |
Lbs. - R410a (outdoor unit) |
|
|
|
| 6.17 | |
Control |
|
|
|
| Electric Expansion Valve | |
Connection |
|
|
|
|
| Flare |
Line Length, Max (ft.) |
|
|
|
|
| 165 |
Lift Difference, Max (ft.) | 50 (outdoor lower), 100 (outdoor higher) | |||||
Line Size |
|
|
| (in. O.D. Discharge) | 3/8” | |
Line Size |
|
|
| (in. O.D. Suction) | 5/8” | |
Dimensions |
|
| (in.) |
| H x W x D | |
Indoor Unit | (Uncrated) |
| ||||
Outdoor Unit | (Crated) |
|
| |||
(Uncrated) |
|
| ||||
| (Crated) |
|
| |||
Weight |
|
|
| Indoor |
| Outdoor |
Net | (lbs.) | 60 |
| 143 | ||
Shipping | (lbs.) |
|
| 71 |
| 161 |
Shipping Volume |
|
|
| Indoor |
| Outdoor |
(cu.ft.) |
|
| 10.6 |
| 13.0 | |
Performance Data @ ARI Standard Conditions (230/208V) | ||||||
Cooling |
|
|
|
|
|
|
Total Capacity |
|
|
| (BTU/H) | 32,600 | |
Sensible Capacity |
|
|
| (BTU/H) |
| 20,160 |
Latent Capacity |
|
|
| (BTU/H) |
| 12,440 |
SEER |
|
|
|
|
| 14.6 |
Dehumidification |
|
|
| (Pints/H) |
| 10.6 |
Amps |
|
|
| (A) |
| 18.7/20.7 |
Power Inputs |
|
|
| (W) |
| 3,950/3,950 |
Outdoor Sound Rating |
|
|
| 52 |